7.2 Inverter demand response modes (DRED)
The inverter shall detect and initiate a response to all
supported demand response commands , demand response
modes are described as follows:
Mode
Requirement
DRM 0 Operate the disconnection device
DRM 1 Do not consume power
DRM 2 Do not consume at more than 50% of rated power
DRM 3
Do not consume at more than 75% of rated power
AND Source reactive power if capable
DRM 4
Increase power consumption (subject to
constraints from other active DRMs)
DRM 5 Do not generate power
DRM 6 Do not generate at more than 50% of rated power
DRM 7
Do not generate at more than 75% of rated power
AND Sink reactive power if capable
DRM 8
Increase power generation (subject to constraints
from other active DRMs)
The RJ45 socket pin assignments for demand response modes
as follows:
DRMS application description
•
Only applicable to AS/NZS4777.2:2015.
•
DRM0, DRM5, DRM6, DRM7, DRM8 are available.