User Manual UM_ASW3000-5000H-S_EN_V01_0321 31
ASW3000H-S/3680H-S/4000H-S/5000H-S
Object Description
Value
A
External diameter
10 to 16 mm
B
Conductor cross-section
4 to 6 mm²
C
Stripping length of the
insulated conductors
approx. 13 mm
D
Stripping length of the outer
sheath of AC cable
approx. 53 mm
The PE conductor must be 2mm longer than the L and N
conductors
Larger cross-sections should be used for longer cables.
Cable design
The conductor cross-section should be dimensioned to avoid
power loss in cables exceeding 1% of rated output power.
The higher grid impedance of the AC cable makes it easier to
disconnect from the grid due to excessive voltage at the feed-in
point.
The maximum cable lengths depend on the conductor cross-
section as follows: