Alarm Behavior Table
Fault
Code
Protect
Function
Active
Mode
Condition
Warning
(O/P=ON)
Fault
(O/P=OFF)
Restart
Operate
Condition
--
Low DC
Voltage
Alarm
Inv. mode
DC
voltage<Low
DC Alarm
1beep/2s
--
--
--
1
Over
Charge
Protection
Line mode
DC
Voltage>High
DC input
Shut-down
Beep
continuous
--
Manual
--
1
Over
Voltage
Protection
Standby
DC
Voltage>High
DC input
Shut-down
--
Beep
continuously
Auto
DC
Voltage<High
DC input
Shut-down
Recovery
2
Over Load
Protection
Line/
Inv. mode
110%~150%
rated load
1beep/0.5
s,and
continue
for10s
Beep
continuously
Manual
--
>150% rated
load
1beep/0.5
s,and
continue
for 5s
Beep
continuously
Manual
--
3
Output
Short
Circuit
protection
Inv. mode
Output
Voltage<20Vr
ms
--
Beep
continuously
Manual
--
4
Inverter
Fan Fault
Protection
Line/
Inv. mode
Fan Locked
Fan Defected
2beep/2s,
and
continue for
1min
Beep
continuously
Manual
--
5
Inverter
Over
Temp
Protection
Line/
Inv. mode
HEAT SINK
over temp
--
Beep
continuously
Auto
HEAT SINK
Temp
≤
55
6
Output
Abnormal
Inv. mode
(Output
Voltage
<170Vrms and
output current
under 32Arms)
or Output
Voltage
>280Vrms
--
Beep
continuously
Manual
--
7
Bus Over
Protection
Standby/
Line/
Inv. mode
Bus voltage
over/ AC
Input and
output
reconnect
--
Beep
continuously
Manual
--
11
SCC
charger
over
current
SCC
SCC charger
current over
120A
--
Beep
1time/2Seco
nd
Manual
--