6. Operation

6. Operation

.64.

.63.

NOTE: 

5G products support lead-acid battery. Select "Lead-Acid" in the 
"Battery Select" and configure the following parameters according 
to different lead-acid batteries.

Settings

Lead Acid Battery

2015-02-23   19 35

Battery Capacity:
Floating

 Voltage:

Floating Current:
I_Max Discharge:
I_Max Charge:

Equalizing Voltage:

Force Charg Voltage

:

100Ah

53.5V
04.0A

010.0A

E S C

U P

D O W N

E N T

060.0A

Overdischg Voltage

:

56

.

4V

44

.

5V

43

.

8V

S E T

=

< E N T >

   

D O N E

=

< E S C >

Lead Acid Battery (Values are examples Only)

Temp.Compensation:

072mV/degC

1. Battery Capacity: Define the capacity of the battery.

2. Equalizing Voltage: Define the voltage for Equalizing/Absorption charge.

3. Floating Voltage: Define the voltage for floating charge.

4. Floating Current: Define the current for floating charge.

5. Overdischg Voltage: Define the voltage that stops discharging the battery.

6. Force Charg Voltage: Define the voltage that forces to charge the battery 

    to prevent a dead battery.

7. ForceChg Limit:Define the battery charge current limit in force charge 

    status.

8. I_Max Discharge: Define the max discharge current for the battery.

9. I_Max Charge: Define the max charge current for the battery.

10. Temp.Compensation: Define the temperature compensation parameter 

       for the battery.

11. AMB.Temp.Lower/Upper: Define the temperature range when the 

      temperature compensation is effective.

After configuration, save and send. 

If battery temperature sensor is connected, select "Warm".

If battery temperature sensor is not connected, select based on actual 

condition for fixed compensation 

Cold: 5 degC     Warm: 25 degC     Hot: 40 degC

ForceChg Limit:

010.0A

AMB.Temp.Upper:

+45degC

AMB.Temp.Lower:

 

+05degC

Settings

Battery

 

Select

2015-02-23   19 35

Y E S

=

< E N T >

   

N O

=

< E S C >

E S C

U P

D O W N

E N T

OverDischg

 

SOC

020

%

Figure 6.34 Over Discharge SOC.

Figure 6.35 ForceCharge SOC

Settings

Battery

 

Select

2015-02-23   19 35

Y E S

=

< E N T >

   

N O

=

< E S C >

E S C

U P

D O W N

E N T

ForceCharge SOC

010

%

ForceChg Limit

100.0A

Содержание S5-EH1P-L

Страница 1: ...712 P R China Tel 86 0 574 6578 1806 Fax 86 0 574 6578 1606 If you encounter any problem on the inverter please find out the inverter S N and contact us we will try to respond to your question ASAP Ve...

Страница 2: ...ion 4 6 AC Cable Installation 4 7 Communication Cable Installation 6 Operation 6 1 Initial Display 6 3 Information 6 4 Settings 6 5 Advanced Info 03 56 6 6 Advanced Settings Technicians Only 2 3 Notic...

Страница 3: ...ttery Cable x2 Connector x1 Terminal cover x1 Rs485 Meter cable x1 For Eastron Meter The Solis S5 EH1P L Series is designed for residential hybrid systems which can work with batteries to optimize sel...

Страница 4: ...sconnecting all power sources service technician only Warranty may be voided if the cover is removed without authorization CAUTION The surface temperature of the inverter can reach up to 75 167 F To a...

Страница 5: ...to the instructions stated in this manual 4 The inverter must be installed according to the correct technical specifications 05 06 Figure 3 3 Front Panel Display WARNING Please refer to the specifica...

Страница 6: ...heating always make sure the flow of air around the inverter is not blocked A minimum clearance of 300mm should be kept between inverters or objects and 500mm clearance between the bottom of the machi...

Страница 7: ...ft up the inverter be careful to avoid injury and align the back bracket on the inverter with the convex section of the mounting bracket Hang the inverter on the mounting bracket and make sure the inv...

Страница 8: ...make sure the PV array open circuit voltage is within the limit of the inverter Before connection please make sure the polarity of the output voltage of PV array matches the DC and DC symbols Please...

Страница 9: ...eard to prove the connection is correct CAUTION If DC inputs are accidently reversely connected or inverter is faulty or not working properly it is NOT allowed to turn off the DC switch Otherwise it m...

Страница 10: ...please carefully read the user manual of the battery and perform the installation exactly as the battery manufacturer requests Figure 4 16 Figure 4 17 A Connector Body A 1 Barrel sealing Not included...

Страница 11: ...imping tool Manual hydraulic crimping Die 25 mm 18 17 Grommet Back shell Correct direction The chamfer in the rear position Wrong direction The chamfer at the front position When 16mm cable apply asse...

Страница 12: ...0 14mm 6 8mm 9mm Traverse cross sectional area Exposure Length Numerical value There are two AC terminals and the assembly steps for both are the same Take out the AC connector parts from the packagin...

Страница 13: ...normal hybrid control logics 1 Optional To realize Demand Response or Logic interface function this function may be required in UK and Australia 1 Optional Used for Solis Data Logger Connection 2 Opt...

Страница 14: ...the positive or negative pole of the battery module 4 7 3 2 Compatible Smart Meter RS485 Connection Compatible Smart Meter Model SDM120CT Default Pin 9 RS485B Pin 10 RS485A Pin 9 RS485B Pin 10 RS485A...

Страница 15: ...s Data Logger Installation 1 Remove the watertight cap from the COM port 2 Insert the Solis Data Logger to the COM port to match the joint NOTE Solis hybrid inverter is designed to provide 12V power f...

Страница 16: ...1 section describes the connection diagram of 1ph meter Eastron SDM120CT and Acrel ACR10R D16TE Below 4 8 2 section describes the connection diagram of 3ph meter Eastron SDM630MCT and Acrel ACR10R D16...

Страница 17: ...PV strings CB Battery CB PV strings CB Battery CB S5 EH1P L Back up L N PE L N PE Grid L N PE CB CB N L S5 EH1P L Distribution box RS485 Meter COM Critical Load RCD RCD PE N L Load_a CT L N PE GRID R...

Страница 18: ...H1P L Back up L N PE La N PE Grid Distribution box RCD RCD RS485 PE N L Load_a L N PE PE N La Load_b Lb Lc PE N Lc Load_c RCD RCD GRID RS485 Lc Lb La N PE CTc CTb CTa N La Lc Lb La N Meter 1 2 3 4 131...

Страница 19: ...ure all the devices are accessible for operation maintenance and service Check and confirm that the inverter is firmly installed Space for ventilation is sufficient for one inverter or multiple invert...

Страница 20: ...DK2 EN50438L C10 11 NRS097 CEI 021 RD1699 EN50549 G98 G99 G98NI G99NI EN50549IE Belgium South Africa Italy Spain Applicable in some European countries UK UK North Ireland North Ireland Ireland France...

Страница 21: ...n Discharge Limitation 000 0A 000 0A Equalizing Charge 055 0V 000 0V 056 4V 046 0V SET ENT DONE ESC Voltage Droop Disable Step 3 7 Select the battery option and set battery SOC The default setting for...

Страница 22: ...rge Time Discharge Time Discharge Time Discharge Time HH MM HH MM 10 00 00 00 00 00 14 00 00 00 00 00 Total Time Total Time Total Time Total Time Total Time Total Time HH MM NEXT ENT DONE ESC Stop Set...

Страница 23: ...te RS485 ON OFF Step 1 Settings Storage Energy Set 2015 02 23 19 35 Control Parameter Battery Select Storage Mode Select Battery Wakeup Meter Set Step 2 Settings Meter Set 2015 02 23 19 35 Meter Selec...

Страница 24: ...ay When powering up the inverter for the first time it is required to set the language Press ENT to select Figure 6 2 Set Language Settings Set Language 2015 02 23 19 35 English YES ENT NO ESC ESC UP...

Страница 25: ...cal Loads Loads connected to the AC Backup port which will be supported by battery and solar even if the grid is in malfunction Grid The arrow and value indicate the export import power of the hybrid...

Страница 26: ...indicates discharging NOTE Information for PV Inverter Meter is only available when two Eastron meters are used and Meter Placement is selected as Grid PV Meter Details please consult Solis service d...

Страница 27: ...yield calculation If Solis monitoring system is used must set the correct time zone of the system otherwise datalogger will update the inverter time based on the time zone of the system Press UP and D...

Страница 28: ...Version and Software Version Battery Enable Disable 6 5 Advanced Information Detailed information can be viewed in this section 1 Alarm Message 2 Running Message 3 Version 4 Communication Data 5 Dail...

Страница 29: ...ly Energy Figure 6 18 Daily Energy Daily Energy 2015 02 23 19 35 2015 23 02 00 10 20 30 40 50 60 D a i l y E n e r g y k W 00 00 03 00 06 00 09 00 12 00 15 00 18 00 21 00 00 00 ESC UP DOWN ENT The scr...

Страница 30: ...arning Message 2015 02 23 19 35 Message Date Time Data NO message ESC UP DOWN ENT 6 5 9 Warning Message Figure 6 22 Warning Message Settings 6 5 8 Total Energy The screen shows the inverter total ener...

Страница 31: ...erter which are subject to change It is for your reference only If customer has any doubts or uncertainty please consult Solis service department for confirmation Detailed protection limits can be vie...

Страница 32: ...Reset Password Calibrate 2015 02 23 19 35 Total Energy Power Parameter 6 6 3 Calibrate By using our data monitoring hardware the data on monitoring website can automatically synchronize with the pres...

Страница 33: ...when the ForceCharge SOC is reached inverter will charge the battery using the power from either PV or Grid ForceChg Limit 0A 100A default 100A Determine the battery charge current limit when inverter...

Страница 34: ...Force Charg Voltage Define the voltage that forces to charge the battery to prevent a dead battery 7 ForceChg Limit Define the battery charge current limit in force charge status 8 I_Max Discharge De...

Страница 35: ...Meter Model Acrel 3ph meter With CT ACR10R D16TE4 Optional Eastron 1ph meter Direct Insert SDM120M Optional Eastron 1ph meter With CT SDM120CT Eastron 3ph meter Direct Insert SDM630 Optional Eastron...

Страница 36: ...HH MM HH MM 10 00 00 00 00 00 14 00 00 00 00 00 Total Time Total Time Total Time Total Time Total Time Total Time HH MM NEXT ENT DONE ESC Stop Charging from gird self use Path Advanced Settings Storag...

Страница 37: ...es from PV If Charging From Grid is allowed it can also come from Grid If Time of Use is Run the logic will follow the charging discharging settings and time settings as defined in Time of Use For tho...

Страница 38: ...g 1 3 are only valid when Setting 2 is set to ON ON OFF is to enable disable the export power control function Backflow Power is to set the max allowed export power at the meter location Failsafe ON O...

Страница 39: ...tdown once it loses communication with the meter in case of any backflow power exceeding the limit 6 6 8 HMI Update This function is used to update HMI software Values are for reference only Figure 6...

Страница 40: ...23 19 35 AFCI Set EPS Mode YES ENT NO ESC 6 6 11 1 AFCI Set Inverters have the built in AFCI function which can detect the arc fault on the DC circuit and shut down the inverter to prevent a fire disa...

Страница 41: ...S switching box to achieve ATS switching function When grid is available only the Grid Port is enabled and load is supported through NPS box by the grid When grid is lost Grid Port will be disabled an...

Страница 42: ...rter has been subjected to several test to ensure its optimal operation and reliability In case of a failure the LCD screen will display an alarm message In this case the inverter may stop feeding ene...

Страница 43: ...it OV G F01 UN G F01 G PHASE G F GLU NO Grid OV G V02 OV G V03 IGFOL F OV G V05 OV G V04 UN G V02 OV G F02 UN G F02 NO Battery Grid frequency exceeds the upper frequency range Grid frequency exceeds t...

Страница 44: ...ATA 0000 UN TEM 103A DATA 0000 PV ISO PRO01 1033 DATA 0001 PV ISO PRO02 1033 DATA 0002 12Power FAULT 1038 DATA 0000 ILeak PRO01 1034 DATA 0001 ILeak PRO02 1034 DATA 0002 ILeak PRO03 1034 DATA 0003 ILe...

Страница 45: ...sists please contact your local distributor or the service center 1 Serial number of Solis Single Phase Inverter 2 The distributor dealer of Solis Single Phase Inverter if available 3 Installation dat...

Страница 46: ...leading 0 8 lagging 96 5 Max output current 15 0 A 14 5 A 18 5 A 17 5 A THDi 2 Efficiency AC grid frequency range Rated grid output current 13 7 A 13 1 A 45 55 Hz 55 65 Hz 16 4 A 15 7 A The grid volta...

Страница 47: ...ange Frequency range 187 265V 31 5 A 30 0 A 45 55 Hz 55 65Hz Max input current 20ms Rated output power 5kW 4 6kW Max apparent output power 4 6kVA Output AC Grid side Power Factor Max efficiency EU eff...

Страница 48: ...ms Li ion Lead acid 100A 5kW Features Quick connection plug AC connection Communication Warranty RS485 Optional Wi Fi GPRS 5 years standard extand to 20 years Display 7 0 LCD color screen display Grid...

Страница 49: ...NE 206007 1 CEI 0 21 C10 11 NRS 097 2 1 TOR EIFS 2018 2 IEC 62116 IEC 61727 IEC 60068 IEC 61683 EN 50530 MEA PEA Safty EMC standard IEC EN 62109 1 2 EN 61000 6 2 3 3000m Max operation altitude MC4 con...

Отзывы: