DOCUMENT NO:
ZL-HOA-4-8 REV. 1 Copyrights
1997
SOLIDYNE CORP
. 4215 KIRCHOFF ROAD , ROLLING MEADOWS ILL. 60008 USA TEL 847-394-3333 FAX 847-394-8083 PAGE -
8
Output-1 Load Relay
FIGURE 6: HOA-5 Single transformer for load relays and IZAC
EXTERNAL
STEP DOWN
Transformer
24VAC Input
Voltage.
24 VAC
INPUT
N.C.
N.O.
24VAC
Coil Input
To Normally Open load
connection.
To Normally Closed load
connection.
Pins 19 and 21 must be connected,
for the HOA LEDs to function when
power is applied to the output.
OUT 1 Common
OUTPUT - 1
OUT 2 Common
OUTPUT - 2
OUT 3 Common
OUTPUT - 3
OUT 4 Common
OUTPUT - 4
No Connection
24
VAC
HOT
24
VAC
RET
24
VAC
INT
24
VAC
INT
GRD
24VAC
INT
Common
Feed-
back
Cntr 0-
10VDC
Manual
0-10V
+12VDC
24VAC
Ext
24VAC
Ret
24VAC
INT
OUT 1
Common
OUT 2
Common
OUT 3
Common
OUT 4
Common
No
Contact
24VAC
EXT
24VAC Ret
24VAC
INT
IN 1
IN 1 Com
IN 2
IN 2 Com
IN 3
IN 3 Com
IN 4
IN 4 Com
No Contact
MANUA
L
ANALO
G
AUTO
OFF
ON
POW
ER
ON
O
O
O
O
O
O
O
J1
J2
JB1
1
JB2
1
2
3
4
J3
&
J4
XMT
RCV
C
C
R
J5
BATTERY
DU-1
CONNECTION
IZAC 4
24 INT
Com
N/O
OUT1
N/C
JP
This JP jumper configuration will allow the IZAC to
produce 24VAC on output 1 when the relay is energized or
a N/O dry contact between the output and output common,
when J2 is removed.
J1 jumper provides power to the IZAC. With J2 in place
the load uses the same 24VAC that is supplying power to
the IZAC. When J2 is removed, the JP jumper
configuration produces a Normally Open, dry contact
between Output 2 and Output 2 common.
NOTE:
The Output Common will always
be HOT when jumped as shown for
Output 1, with J2 in place and JP's 24
INT jumped to Com.
HOA status LEDs will be ON
when power is applied to the
Output, dry contact will not
light the HOA LEDs.