DOCUMENT NO: 

ZL-HOA-4-8 REV. 1  Copyrights 

 1997

 

 SOLIDYNE CORP

. 4215 KIRCHOFF ROAD , ROLLING MEADOWS ILL. 60008  USA     TEL 847-394-3333    FAX 847-394-8083  PAGE -

3

Mechanical :

Each Board is 4.00” wide X 2.350” long X 1.000” high

----------See figure 3------------

Environmental

 :

Operation Temp range : 10 to 140 

°

 F

Storage : -10 to 160 

°

 F

Operation Humidity : 0 - 95% RH non-condensing
Storage    Humidity : 0 - 100% RH non-condensing

INSTALLATION AND WIRING :

The HOA-5 and -9 should be mounted indoors, if possible.  If the
units must be mounted outside, make certain they are installed
inside a well protected Electrical Enclosure that is free from
moisture and contact with the elements.

If it the HOA-5 is to be used with the IZAC-4 Controller or the
HOA-9 with  the IZAC-8 Controller, the best way to install them is
as follows:

1.  

First, mount the plastic tracks for both the Controller and HOA
horizontally, so that the tracks line up.

2.  

Place the Controller and HOA into the track and
insert one side of the one-piece connector into the
Controller output and slide the HOA's input over
the other side of the connector.  The Controller's
output connections will be directly opposite the
HOA's inputs.  18 AWG wire can also be used to
connect the Controller output to the HOA input.
After the positioning the units close together over
the connector, tighten the terminal screws.

WIRING:

(See Figures 1 and 2  for references made to the pin
numbers)

HOA pins 1, 2, 3 are the 24VAC connections to the
Controller.  HOA pins 20, 21, 22 connect through to
pins  1, 2, and 3, respectively.  The connection from pin
1 to 20 provides a path for the External 24VAC 

HOT

,

used by the Controller.  The 24VAC supply transformer
is protected between pins 1 and 20 with a fuse and
transorb.  Pin 2 connects to pin 21, providing the path
for the 24VAC Return(or neutral). The connection
between pins 3 and 22 is the path for the IZAC
Controller's 24VAC Internal 

HOT

(or Input  24VAC

HOT

), taken from another 24VAC source transformer

to drive the 24VAC loads.

Each output of the HOA-5 Module has a dedicated pair
of Output and Output Common terminals for each load
connection.  The outputs of the HOA-9 Module have
only one Output Common, shared by all of the
individual load connections. Load connections from the
Controller to the HOA-5, and -9 are made through these
terminals for the respective Controller loads.

Pins 13 to 19 have the same designation for both the
HOA-5 and HOA-9.  Pins 13 and 14 provide the
override feedback to the Controller.  Pin 14 connects
to one of the controller's 0-10V sensor inputs, pin 13
connects to sensor common.  The 0-10V output from
the Controller would connect to pin 15 on the HOA.
The Controller's 0-10V output would then be taken
from pin 16 on the HOA(the 0-10V common would
come directly from the Controller).  Provide Pin 17 with 
an unreg12- 18VDC, rated for 30mA.  Pin 13 is
common for this output.  Pin 18 connects to a good
earth-ground, and is critical for proper transient circuit
protection.  Pin 19 is the 24VAC internal relay return.

FIGURE 1: HOA Mounting

Содержание HOA-5

Страница 1: ...olid state reset able 3 Amps fuses Power to the module and each output channel has a high intensity Light Emitting Diode LED status indicator The output LEDs are ON when the output is energized Automa...

Страница 2: ...d on and especially switched off can generate a very sharp voltage spikes eventually producing damaging arcing at a high frequency due to rate of change of voltage Electrical noise can travel over the...

Страница 3: ...re the 24VAC connections to the Controller HOA pins 20 21 22 connect through to pins 1 2 and 3 respectively The connection from pin 1 to 20 provides a path for the External 24VAC HOT used by the Contr...

Страница 4: ...SW 1 LED 1 INPUT 8 OUTPUT 8 N O N C ELECTRONIC CIRCUITRY 0 10 VDC FEEDBACK OUTPUT INPUT 4 OUTPUT 4 FUSE TRANSORB AUTO OFF ON SW 4 LED 4 INPUT 2 FUSE TRANSORB AUTO OFF ON SW 2 LED 2 INPUT 3 OUTPUT 3 FU...

Страница 5: ...NSORB AUTO OFF ON INPUT 1 INPUT 1 COMMON OUTPUT 1 OUTPUT 1 COMMON FUSE TRANSORB AUTO OFF ON GROUND 24 VAC INT RELAY CONTACT RETURN 0 10VDC ANALOG OUTPUT FROM A CONTROLLER 0 10VDC OVERRIDE FEEDBACK COM...

Страница 6: ...Closed load connection J1 and J2 Jumper installed With J2 in place the load uses the same 24VAC that is supplying power to the IZAC Pins 19 and 21 must be connected for HOA LEDs to turn on when power...

Страница 7: ...tion To Normally Closed load connection EXTERNAL STEP DOWN Transformer 24VAC Input Voltage Second 24VAC for load relays Load Relay 24 VAC INPUT J1 J2 JB1 JB2 1 2 3 4 5 6 7 8 J3 J4 XMT RCV C C R J5 BAT...

Страница 8: ...mon OUT 3 Common OUT 4 Common No Contact 24VAC EXT 24VAC Ret 24VAC INT IN 1 IN 1 Com IN 2 IN 2 Com IN 3 IN 3 Com IN 4 IN 4 Com No Contact MANUA L ANALO G AUTO OFF ON POW ER ON O O O O O O O J1 J2 JB1...

Страница 9: ...ys Load Relay 24 VAC INPUT O O O O O O O J1 J2 JB1 1 JB2 1 2 3 4 J3 J4 XMT RCV C C R J5 BATTERY DU 1 CONNECTION IZAC 4 GRD 24VAC INT Common Feed back Cntr 0 10VDC Manual 0 10V 12VDC 24VAC Ext 24VAC Re...

Страница 10: ...1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 IN Com 0 10V In 0 10V Out 0 10VDC Control Signal 0 10VDC controlled device Feedback Voltage Common 12VDC 12VDC IN GND Earth Ground required for proper transient pr...

Страница 11: ...IN Com GRD 24VAC INT Common Feed back Cntr 0 10VDC Manual 0 10V 12VDC 24VAC Ext 24VAC Ret 24VAC INT OUT 1 Common OUT 2 Common OUT 3 Common OUT 4 Common No Contact 24VAC EXT 24VAC Ret 24VAC INT IN 1 IN...

Отзывы: