Operating Voltage

Unit Voltage

Voltage Utilization Range

 Rating

Minimum

Maximum

230/208  187 253

115

103

126

LCDI power Cord

VOLTAGE MEASUREMENTS

Before connecting the unit, measure the supply voltage.

Voltage must fall within the voltage utilization range given 

in Table 1.

115V 230V 230V

15 amp 15 amp 20 amp

Figure 1

• 

LCDI or AFCI Power Cords 

- Underwrites Laboratories

and the National Electric Code (NEC) now require

power cords that sense current leakage and can open

the electrical circuit to the unit on units rated at 250

volts or less.  In the event that unit does not operate,

check the reset button located on or near the head of

the power cord as part of the normal troubleshooting

procedure.

1

IMPORTANT NOTE TO THE OWNER

This equipment is to be serviced by professionally trained

personnel only.  If this equipment is improperly installed,

adjusted or altered by an unqualified person, a safety

hazard may result.

IMPORTANT NOTE TO THE SERVICER

Read this manual and familiarize yourself with the specific

items which must be adhered to before attempting to

service this unit.  The precautions listed in this manual

should not supersede existing practices but should be

considered as supplemental information.

Transportation Damage

All units are securely packed in shipping containers ap-

proved by the National Safe Transit Association.  The carton

should be checked upon arrival for external damage.  If

damage is found, immediately make a written request for

inspection by the carrier’s agent.
In the event of damage:

1. Note on the delivery receipt any visible damage to

shipment or container.

2. Notify carrier promptly and request an inspection.
3. File the claim with the following supporting documents

within the six month statute of limitations.

a. Original Bill of Lading, certified copy, or indemnity

bond.

b. Original paid freight bill or indemnity.
c. Original invoice or certified copy, showing trade and

other discounts or reductions.

d. Copy of the inspection report issued by carrier’s

representative at the time damage is reported to the

carrier.

The carrier is responsible for making prompt inspection of

damage and for a thorough investigation of each claim.  The

distributor or manufacturer will not accept claims from

dealers for transportation damage.

Unpacking The Unit

1. Cut the carton banding and open the carton.
2. Remove the literature, hardware pack, upper styrofoam

shipping blocks, and styrofoam corner posts.

3. Remove the front assembly.
4. Lift the unit from the remaining carton.
5. Dispose of the cardboard and styrofoam at an approved

Recycle Center.  Check all contents for damaged or

missing parts.  In case of concealed damage, notify the

carrier as soon as possible—preferably within 5 days.

Refer to step 3 of the 

Transportation Damage 

section if

damage or missing parts are noted.

Operating  Instructions

Check the data specification plate and ensure the proper

voltage and current rating for the type of power plug on the

unit is available.  DO NOT REMOVE THE GROUNDING

PRONG FROM THE POWER CORD.  See Figure 1 for the

types of acceptable plugs.  Do not use an extension cord

for the installation of this product.  Refer to the data

specification plate for electrical requirements.

Table 1

Operating Voltage

Содержание KTW-08

Страница 1: ...stallation Instructions and Owner s Manual This manual must be left with the owner of the equipment Model KTW 08 10 12 12H 2008 Soleus Air International Thank you for selecting Soleus Air To ensure proper operation please read this manual keep it for future reference ...

Страница 2: ......

Страница 3: ...ealers have a list of specific good safety practices follow them The precautions listed in this Installation Manual areintendedassupplementaltoexistingpractices However ifthereisadirectconflictbetweenexisting practices and the content of this manual the precautions listed here take precedence RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION Contents IMPORTANT NOTE TO THE OWNER 1 IMPORTANT NOTE TO THE ...

Страница 4: ...event of damage 1 Note on the delivery receipt any visible damage to shipment or container 2 Notify carrier promptly and request an inspection 3 File the claim with the following supporting documents within the six month statute of limitations a Original Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity c Original invoice or certified copy showing trade and ...

Страница 5: ...upplied with the wall sleeve for a complete description of the installation proce dure NOTE Wallsleeve PBWS01A isnotshippedwithchassis and must be purchased separately Wall Sleeve Outside Wall Outside Inside Level 1 4 Bubble Tilt To Outside Figure 2 CHASSISINSTALLATION 1 Remove front grille See Figure A Lift up on Filter Handle Figure A Thefrontgrillecanberemovedformorethoroughcleaning or to make ...

Страница 6: ...chassis into the sleeve Ensure thatthegroundwireisnotpinchedorinthepathofthe condenserfan 5 Loosen locking plate screw and rotate tab with tab behind wall case flange See Figure C then tighten locking plate screw Locking Plate Figure C 6 If outlet is on the left side of the unit route power cord as shown in Figure D Clamp Power Cord Figure D ...

Страница 7: ...at OPEN some inside air is exhausted outside Locating Hole Locating Hole Screw Hole Screw Hole OPEN position Mesh end toward back CLOSE position Mesh end toward front Figure E To open or close the vent 1 Removethefrontgrille 2 Remove the vent card screw 3 Remove the vent card turn it over and replace it by locating rear hole in card over locating pin inside air discharge and reattaching screw at f...

Страница 8: ...ng or life support for personsoranimalswhoareunabletoreact to the failure of this product Thefailureofanunattendedairconditioner mayresultinextremeheatintheconditioned space causing overheating or death of persons or animals Take proper precautionstoavoidunattendedoperation DISCHARGE AIR GRILLE Figure 5 IMPORTANTNOTES 1 The unit is equipped with a rubber grommet mounted compressor These grommets a...

Страница 9: ...Do Not Mix Alkaline Standare Carbon Zinc Or Rechargeable Nichel Cadmium Batteries NOTE The remote control will work normally after reset 5 senconds LOWERS TEMPERATURE OR TIME RAISES TEMPERATURE OR TIME SETS FAN SPEED SETS MODE DISPLAYS TEMPERATURE TIME TURNS UNIT ON OR OFF TIMER LOWERS TEMPERATURE OR TIME RAISES TEMPERATURE OR TIME SETS FAN SPEED SETS MODE DISPLAYS TEMPERATURE TIME TURNS UNIT ON O...

Страница 10: ... maintained anywhere between 55F 13 C and 80F 27 C for heating mode If you want the display to read the actual room temperature Select the fan only mode TO CHANGE FAN SPEEDS YOU WILL SEE THE SPEED CHOSEN LIGHT ON LIGHT ON YOU WILL SEE Note The fan speed will begin in HI then adjust to MED and LO as the room temperature conditions indictates For example in cooling if the room doesn t get too warm i...

Страница 11: ...l count down the timer remaining until start 8 7 5 7 etc The Delay Start mode automatically selects cooling with maximum Fan Speed The temperature maintained will be the same as previously set To change the set temperature press COOL then Up or Down arrows until the desired temperature is indicated on the display After 5 seconds the control will automatically change the display back to the hours r...

Страница 12: ...e Control will operate all the control panel features follow the same instructions The control will maintain any set temperature between 60F and 90F degrees cooling 55F and 80F heating The control is capable of displaying temperature in degrees Fahrenheit or degrees Celsius To convert from one to the other press and hold the Up and Down Temperature Selection Pads at the same time for 3 seconds The...

Страница 13: ...ditions theunit should be removed from the sleeve and completely cleaned once a year At that time any scratches or blisters on the painted surfaces should be sanded and repainted OUTDOORCOILCLEANING Thecoilsontheoutdoorsideoftheairconditionershouldbe checked regularly For cleaning outside coil remove the 6 screwsthatmountthecondensercoiltopcovertocondenser shroud NormalOperatingSoundsandConditions...

Страница 14: ...13 5 EER C O P 9 4 9 4 9 4 9 4 Noise Level dB A H M L 58 56 54 58 56 54 60 58 56 60 58 56 CFM 280 280 280 280 Design Pressure PSIG H L 400 psi 170psi 400 psi 170psi 400 psi 170psi 400 psi 170psi Dimension W H D 25 98x15 62x16 88 25 98x15 62x16 88 25 98x15 62x16 88 25 98x15 62x16 88 Packing Dimension W H D 29 64x18 22x24 4 29 64x18 22x24 4 29 64x18 22x24 4 29 64x18 22x24 4 Net Gross Weight Lb 72 26...

Страница 15: ... power line voltage fire flood or other Acts of God or normal wear and tear Warranty service must be performed by a qualified HVAC contractor Soleus maintains a centralized service network to provide parts and assist in resolving service problems if difficulties are encountered Soleus agrees to provide service information sell repair parts and reimburse the dealer serviceman for parts in accordanc...

Страница 16: ......

Отзывы: