(1)
– Left scroll key (-)
(2)
– Right scroll key (+)
(3)
– Validation key
(4)
– Display area
2
4
1
3
Position switch:
nC: normally closed
nO: normally open
Power of communication between the remote control and the IDEO.
Must be more than 50% to a good working.
Test of the installation pressure drop. Test executed at 120m³/h
0N: Activated - 0FF: Disactivated
I00 = Installation OK
I01 = Installation acceptable
I02 = Installation beyond limits (without fouling up of filters ).
Operating point of the installation test. Factory setting. 37%=120 m3/h.
26%=90 m3/h
37%=120 m3/h
44%=150 m3/h
53%=180 m3/h
62%=210 m3/h
70%=240 m3/h
80%=275 m3/h
Speed limit for fouling up filter alarm.
Factory setting: 2750 rpm.
Max: 2850 rpm.
Choice of communication channel between the remote controls and IDEO. Factory setting =
Channel 0
Up to 64 (from 0 to 63).
To modify the channel, see Chapter 2.9.
6.1 - Access to installation menu
Accessing to this menu allows to check and adjust the IDEO's parameters of each installation.
Reset of the factory settings.
Identification of software version remote control
3 seconds
To access to the menu
Parameter blocking (airflows, time etc.):
OFF: Parameters that can be modified by the user.
On: Parameters that cannot be modified by the user.
Temperature display inside the heat recovery unit.
LEFT: “T in” = interior T (on extraction)
MIDDLE: exterior T (air intake).
RIGHT: T out “= discharge T (to the exterior)
bloq
CLP
tl
tE
tESt
PtE
FiLt
tEnP
CHAn
Pouu
rESE
L1-5
M1-7
Indoor temperature parameter ByPass
Factory setting: 24ºC
Adjustment range from 21ºC to 30ºC
Outdoor temperature parameter ByPass
Factory setting: 12ºC
Adjustment range from 11ºC to 20ºC
Identification of software version remote control central unit.