Display By-pass operation/ Free cooling operation in summer (6):
Avoiding the heat exchanger, the system of bypass 100% of IDEO allows the
introduction of fresh air at night without it being heated by contact with hot air
accumulated in the home during the day. The by-pass operates automatically if these
three conditions are true:
Tº in> 12º (modifiable)
Tº in > Tº out
Tº in > 24ºC (modifiable)
It is possible to program a specific rate when the By-pass is in operation. (see
paragraph forced march).
When the bypass is running, the pictogram (6) appears.
•
Forced commissioning of the by-pass (6):
If you want to have the opportunity to manually force for a period of 1 changed to 24
hours (factory setting 8 hours).
You can also change the airflow when the bypass is in operation.
Navigating with buttons 19 or 20 until 6 pictogram bypass. Select with key 18. You can
change the operating time with the keys 19 and 20 . Confirm with 18 .
Select ON using 19 or 20 keys. Confirm with 18. You can change the speed by
pressing 19 and 20
At any time you can disable bypass forced. To do this, Navigate with the buttons 19 or
20 until 6 pictogram bypass.
Select with key 18. Select OFF using keys 19 or 20. Confirm with 18.
Example of programming:
DAY 1 (Monday):
T1: start 6:30h- end 7:30h
T2: no programming
T3: start 19:30h pm - end 20:30 p.m.
Navigate with the arrow keys until 19 or 20 until pictogram 2.
Select "Man." Confirm by pressing 18.
Confirm by pressing again the button 18.
Day 1 flashes. Press 18.
T1 flashes. Press 18.
According to the example, use the buttons 19 and 20 to enter 6:30h. Confirm with 18.
The program will be automatically scheduled for 1H.
T2 flashes. No programming scheduled. Then press 19 to set T3.
Confirm with 18 and use the buttons 19 and 20 to get 19.30. Confirm with 18.
The program will automatically set to 1H
Repeat for each day according to the desired programming.
•
Selection and validation of the
Boost”
In case any of programmable solutions proposed is adopted, it is possible to manage
the
“max airflow” with the Boost.
Navigate with the arrow keys until 19 or 20 until pictogram 2.
Select and confirm by pressing the button 18 Mode "Manu" without setting schedules.
Button "boost" is equipped with a timer 30 '. Airflow function returns "minimum airflow"
at the end of this period.