EXHAUST AND SUPPLY NETWORK
The ducting installation is composed of insulated PVC ducting
The duct layout should be as simple as possible :
- avoid long ducting runs and severe angles or bends
- install the duct with large sweeping bends
- the flexible duct should not be deformed or flattened
The exhaust network consists of Ø125 mm flexible ducting for the kitchen and Ø80 mm for other rooms such as
bathrooms, toilets etc.
The spigot of the exhaust fan is connected to a roof outlet with duct of Ø150 mm.
The supply network consists of derivations Y branch Ø150/ Ø125/ Ø60. In the case of large dwelling, it is possible
to use a derivation Ø150/Ø150/Ø150 in order to realise parallel supply networks
The fresh air intake is done with duct in Ø150 mm.
IMPORTANTADVICE
: cover the overall duct system with a layer of glass wool (70 mm) so as to avoid
condensation.
NUMBERS OF EXTRACT & SUPPLY VALVES
T2/3
T4/T5 T6/T7
GD
EXTRACT
Kitchen valve
Sanitary valve 30 m³/h
Sanitary valve 15 m³/h
1
1
1
1
2
-
1
2
2
1
4
-
SUPPLY
Valves CD
4 to 6 5 to 7 7 to 9 9 to 12
REALISATION OF EXTRACT & SUPPLY NETWORKS
L3
L1
D1
L4
I3
L3
I3
D1
CD
D2
D3
D4
L2
L1
EXHAUST
EP OR ESA
Ø60
Ø 125
Ø 125
Ø 150
Ø 80
Ø 125
Ø
150
Ø
15
0
L1------------------MAXI 6m
L2------------------MAXI 6m
L3------------------MAXI 6M
Possibility n°2
L1 + L2---------------MAXI 6m
L3----------------------MAXI 12 m (with l3 mini 1.5 m)
L4----------------------MAXI 6m
-Possiblity to inctrease L1 & L2 if L3 is < to 12m
-If L3 is < to 12 m L1+L2+L3 MAXI 18m