3. Installation Instructions.
- Cont.
INSTALLATION MANUAL SOLENE
®
HOT WATER SYSTEMS
©
2014 UMA Solar
Normally, collectors are installed on roofs, as close as possible to the tank, to minimize heat loss through the pipe. The pipes between
the tank and the collectors MUST be insulated with at least ¾” thick insulation, for the same reason. Check local codes for well
thickness in your area.
The solar collectors must be located in a structurally sound area of the roof that will be exposed to the sun for the majority of the day,
all year round. A solar pathfinder can be used for solar site analysis.
The recommended angle of the collectors is equal to the location’s LATITUDE. This angle is designed to maximize solar absorption
annually. For increased energy production in
winter
months, the collector angle can be increased up to +15 degrees from latitude.
For increased
summer
energy production, decrease collector angle up to - 15 degrees from latitude. A variation of +/- 15 degrees is
acceptable. The orientation of the collectors must be due south ± 55 degrees. Flush mounts on available roof slopes are recommended
to allow convenience and cost effectiveness, since these variations from the exact angle and orientation will affect the system’s
performance only by about 5%.
INSTALLATION INSTRUCTIONS.
-
4
To comply with SRCC certification the storage tank shall have an additional insulation jacket.
80
1
SLAR-32
Differential Control
SLCO32DC-80HE
2006023A
1.25
80
1
SLAR-40
Differential Control
SLCO40DC-80HE-XE
2006029B
1.21
80
1
SLAR-40
Differential Control
SLCO40DC-80HE-XG
2006025B
0.75
80
1
SLAR-40
Differential Control
SLCO40DC-80HE
2006023B
1.31
80
2
SLCO-30
Differential Control
SLCO60DC-80HE
2006023C
1.45
120
2
SLAR-32
Differential Control
SLCO64DC-120HE-XE
2006029E
2.19
80
2
SLAR-32
Differential Control
SLCO64DC-80HE-XE
2006029C
2.21
120
2
SLAR-32
Differential Control
SLCO64DC-120HE-XG
2006025E
1.19
80
2
SLAR-32
Differential Control
SLCO64DC-80HE-XG
2006025C
1.2
120
2
SLAR-32
Differential Control
SLCO64DC-120HE
2006023F
2.7
80
2
SLAR-32
Differential Control
SLCO64DC-80HE
2006023D
2.85
120
2
SLAR-40
Differential Control
SLCO80DC-120HE-XE
2006029F
2.85
80
2
SLAR-40
Differential Control
SLCO80DC-80HE-XE
2006029D
2.93
120
2
SLAR-40
Differential Control
SLCO80DC-120HE-XG
2006025F
1.44
80
2
SLAR-40
Differential Control
SLCO80DC-80HE-XG
2006025D
1.46
120
2
SLAR-40
Differential Control
SLCO80DC-120HE
2006023G
4.03
80
2
SLAR-40
Differential Control
SLCO80DC-80HE
2006023E
4.47
75
1
SLSG-40
Differential Control
SLSG40DC-75HE-G
30004222
1
75
1
SLAR-40
Differential Control
SLAR40DC-75HE-G
30004221
1
75
2
SLAR-32
Differential Control
SLAR64DC-75HE-G
30004220
1.5
75
1
SLAR-32
Differential Control
SLAR32DC-75HE-G
30004219
0.9
Tank Capacity
(Gallons)
Number of
Collectors
Collector
Type
Control Type
Model Number
SRCC
Number
SEF