14 • Mode Pages Display 

________________________________________________________________________________________________ 

 

6.3

 

Parameter Setting 

 Tripping and Alarm Options 

 

 

 

 
 
 
 
Protection function

 

Each of the TPR-6 Protections can be assigned to each of the following functions :  

1.  TRIP function – ENABLED or DISABLED, if ENABLED can be programmed to TRIP or TRIP-FAIL 

SAFE function (see I/O SETTINGS page) 

2.  ALARM function – ENABLED or DISABLED  
3.  AUTO RESET – Enabled or Disabled 
4.  Operate RELAY A – ENABLED or DISABLED 
5.  Operate RELAY B – ENABLED or DISABLED 
6.  Operate RELAY C – ENABLED or DISABLED 
7.  Operate RELAY D – ENABLED or DISABLED 

 

 
Each of the TPR-6 Protections has two levels – LEVEL 1 and LEVEL 2 

The following represents the displays shown for level 1 of the first temperature sensor. Similar displays are 
shown for all sensors with LEVEL 1 faults then for all sensors with LEVEL 2 sensors. 

Note

: If a sensor is set as NOT USED, then only one screen (per Level) for this sensor will be displayed, 

showing NOT USED. 
 
Press

 

SELECT

 

 
 
 

 

Enabling, Disabling trip function for T1 LEVEL 1. 
Press 

▲ or▼

 keys to set if TRIP is after T1 LEVEL 1.  

Range: DISABLE, ENABLE  

 

Press

 

SELECT

 

 
 
 

 

Enabling, Disabling Alarm function for T1 LEVEL 1. 
Press 

▲ or▼

 keys to set if ALARM is after T1 LEVEL 1.  

Range: DISABLE, ENABLE 

 

Press

 

SELECT

 

 
 
 

 

Enabling, Disabling auto-reset function for T1 LEVEL 1 
Press 

▲ or▼

 keys to set if T1 LEVEL 1 is AUTO RESET or not AUTO RESET.  

Range: DISABLE, ENABLE 

 

Press

 

SELECT

 

 
 
 

 

Enabling, Disabling operation of RELAY A for T1 LEVEL 1. 
Press 

▲ or▼

 keys to set if RELAY A will follow T1 LEVEL 1 settings. 

Note

: Relay operates upon T1 LEVEL 1 fault which is enabled if RELAY A is set to TRIPPING/ALARM in the 

I/O SETTING PAGE.  
Range: DISABLE, ENABLE 

TRIPPING / ALARM

 

*** OPTIONS ***

 

T1  LEVEL 1 
TRIP: DISABLE 

T1  LEVEL 1 
ALARM: ENABLE 

T1  LEVEL 1 
AUTO RST: DSABL 

T1  LEVEL 1 
RELAY A: DISABLE 

RELAY A, RELAY B, RELAY C and RELAY D must 
be configured as TRIPPING/ALARM in the I/O 
SETTING PAGE in order to operate in the 
TRIPPINNG/ALARM mode. 

Refer to section 

9 - Tripping / Alarm Default Settings on page 22 for the default settings 

of all the parameters in the TRIPPING/ALARM OPTIONS mode page.

 

Содержание TPR-6

Страница 1: ...T TP PR R 6 6 T Te em mp pe er ra at tu ur re e P Pr ro ot te ec ct ti io on n R Re el la ay y I In ns st tr ru uc ct ti io on n M Ma an nu ua al l Ver June 1st 2010...

Страница 2: ...Information 27 15 Notes 28 Safety notes Read this manual carefully before operating the equipment and follow its instructions Installation operation and maintenance should be in strict accordance wit...

Страница 3: ...t in degrees C for RTD type sensors or K for Thermistor type sensors Time delay level 1 A time delay can be set for level 1 Time delay level 2 A time delay can be set for level 2 Group of sensors Used...

Страница 4: ...e digital parameters setting actual parameters readings and detailed trip and alarm message displays Changes can easily be prevented by the usage of the parameter lock feature RS485 serial link with M...

Страница 5: ...roup together with the RS 485 communication When using both connections verify that analog out user or RS 485 user is using an isolated circuitry Connect all shield wires to ground a short busbar may...

Страница 6: ...d as Alarm the relay de energizes This relay can be used to sense control supply outage TRIPPING ALARM Relay can be assigned to specific faults that are enabled as alarm or trip Common 1 N C 2 N O 3 O...

Страница 7: ...RTD 6 66 67 68 For a 14 thermal inputs Thermistor 7 21 22 RTD 7 21 22 23 Thermistor 8 24 25 RTD 8 24 25 26 Thermistor 9 27 28 RTD 9 27 28 29 Thermistor 10 30 31 RTD 10 30 31 32 Thermistor 11 33 34 RT...

Страница 8: ...ne will appear under the first letter of the lower line for example RTD Press once to increase parameter value Press and hold to increase value at a fast rate Press once to decrease parameter value Pr...

Страница 9: ...e minutes this parameter will be constantly displayed 2 A new parameter setting becomes effective upon setting even before storing it in the non volatile memory However setting a parameter without sto...

Страница 10: ...f Tx SENSOR TYPE is set to RTD this display is in deg C Celsius degrees If Tx SENSOR TYPE is set to PTC THERMISTOR or NTC THERMISTOR this display is in kOHM Press or keys to set Tx LEVEL 1 value Range...

Страница 11: ...r all sensor channels Press or keys to set time delay Range 0 1 20 Sec Press SELECT Any sensor 1 14 can be grouped for group measurement and analogue output Press or keys to set whether the temperatur...

Страница 12: ...P the relay changes position upon trip and returns to original position upon reset after fault has been removed TRIP FAIL SAFE the relay changes position upon voltage connection and return to original...

Страница 13: ...e modified Press or keys to lock unlock parameters settings Range NOT LOCKED LOCKED Press SELECT When locked parameters can be reviewed but not modified via the communication link When unlocked parame...

Страница 14: ...nsor will be displayed showing NOT USED Press SELECT Enabling Disabling trip function for T1 LEVEL 1 Press or keys to set if TRIP is after T1 LEVEL 1 Range DISABLE ENABLE Press SELECT Enabling Disabli...

Страница 15: ...keys to set if EXTERNAL FAULT 1 is set to TRIP the unit Range DISABLE ENABLE Press SELECT to see ALARM AUTO RST RELAY A RELAY D settings for EXTERNAL FAULT 1 Press SELECT Enabling Disabling trip funct...

Страница 16: ...upon communication failure Press or keys to set this function Range DISABLE ENABLE Press Select to see Alarm AUTO RST RELAY A RELAY D settings for COMM PORT FAILED Press SELECT Enabling Disabling tri...

Страница 17: ...SOR TYPE is set to PTC THERMISTOR T3 SENSOR TYPE is set to PTC THERMISTOR Press SELECT In case sensors are not connected the LCD will show FAILED SENSOR Press SELECT In case sensors are not connected...

Страница 18: ...25 5 KOHM R3 MAX VALUE 25 5 KOHM R3 AT TRIP TIME 0 KOHM 255 deg C Note When in the STATISTICAL DATA displays pressing RESET for more than 1 second will zero the display screen More than One Alarm or T...

Страница 19: ...STORE PAGE keys simultaneously Note All values set by you will be erased Display will show Press SELECT If it is required to reset all STATISTICAL DATA press STORE RESET keys simultaneously Note All...

Страница 20: ...electrical shock or damage to the TPR 6 before dismantling the TPR Main PCB All models Input PCB TPR 6 14 only Close look on dip switches S1 S2 PT100 Thermistor inputs T1 T6 All models are designated...

Страница 21: ...done 1 Identify the Main PCB in All models and Input PCB TPR 6 14 only 2 Remove four screws holding the back cover of the TPR 6 and remove the cover 3 Hold the Input PCB by the two sides of the connec...

Страница 22: ...T1 LEVEL 1 Always 49R 2 T2 LEVEL 1 Always 49R 3 T3 LEVEL 1 Always 49R 4 T4 LEVEL 1 Always 49R 5 T5 LEVEL 1 Always 49R 6 T6 LEVEL 1 Always 49R 7 T7 LEVEL 1 Always 49R 8 T8 LEVEL 1 Always 49R 9 T9 LEVE...

Страница 23: ...e key If an error is found during store process then next message is shown STORAGE ERROR Displayed when an error is found in the store process WRONG PARAMETERS Displayed after power up if the non vola...

Страница 24: ...and continuous updates of performance parameters Load control can be performed from host computers or by PLCs The following information and control can be accessed through the communication All Actua...

Страница 25: ...K Time delay 2 Sec Accuracy 3 of full scale resistance Max wire resistance 25 of Sensor resistance at 10 deg C Fault Time Delays Accuracy 0 5 Sec or 2 of time which ever is greater for all but the ab...

Страница 26: ...6 Dimensions and Cut Out Dimensions ________________________________________________________________________________________________ 13 DIMENSIONS AND CUT OUT DIMENSIONS 86 4 107 Cut Out 92 138 144 96...

Страница 27: ...uts Specify Description 6 6 Temperature Inputs 14 14 Temperature Inputs Supply Voltage Specify Description 2 110 240V 50 60Hz or DC 10 15 Communication Specify Description M RS485 with MODBUS protocol...

Отзывы: