12 • Mode Pages Display
________________________________________________________________________________________________
6.2
Parameter Setting
–
I/O Settings
Press
SELECT
Configure Alarm Relay function
Press
▲ or▼
keys to set required operation mode
Range: ALARM, ALARM FAIL SAFE, TRIPPING/ALARM
ALARM
- the relay changes position upon trip and returns to original position upon reset, after fault has been
removed.
ALARM FAIL SAFE
- the relay changes position upon voltage connection and returns to original position
upon fault.
TRIPPING / ALARM -
Relay can be assigned to specific faults that are enabled as alarm or trip.
Press
SELECT
Configure Trip Relay function
Press
▲ or▼
keys to set required operation mode
Range: TRIP, TRIP FAIL SAFE, TRIPPING/ALARM
TRIP
- the relay changes position upon trip and returns to original position upon reset, after fault has been
removed.
TRIP FAIL SAFE
- the relay changes position upon voltage connection and return to original position upon
fault.
TRIPPING / ALARM -
Relay can be assigned to specific faults that are enabled as alarm or trip.
Press
SELECT
Configure input 1 function
Press
▲ or▼
keys to set required input function for INPUT 1.
Range: REMOTE RESET, EXTERNAL FAULT 1 N.O., EXTERNAL FAULT 1 N.C.
Press
SELECT
Configure Trip Relay function
Press
▲ or▼
keys to set required input function for INPUT 2.
Range: REMOTE RESET, EXTERNAL FAULT 2 N.O., EXTERNAL FAULT 2 N.C.
Press
SELECT
Configure Analogue Output
Press
▲ or▼
keys to configure the analog output.
Range: 0-20mA NORMAL, 4-20mA NORMAL, 0-20mA INVERTED and 4-20mA INVERTED
I / O
*** SETINGS ***.
CONFIG. TRIP REL
TRIP
CONFIG. INPUT 1
REMOTE RESET
CONFIG. INPUT 2
REMOTE RESET
CONFIG. ANLG OUT
4-20mA NORMAL
CONFIG. ALARM REL
ALARM FAIL SAFE