Installation Notes

 

 
 

 

 

Prior to Installation 

Check that Motor's Full Load Ampere (FLA) is lower than 
or equal to Solbrake / SMB Full Load Current (FLC) and 
verify that Mains voltage and frequency are as indicated on 
the Solbrake / SMB label. 
 

Mounting 

*  The Solbrake / SMB must be mounted vertically, allow 
    space above and below the unit for sufficient airflow. 
*  It is recommended to mount the SMB directly on the rear 

metal plate for better heat dissipation. 

Do not mount the Solbrake / SMB near heat sources. 

Protect the Solbrake / SMB from dust and corrosive 

    atmosphere. 

Temp. Range and Heat Dissipation 

The Solbrake / SMB is rated to operate over a temperature 
range of  -10

°

C (14

°

F) to +50

°

C (122

°

F). 

Relative non-condensed humidity inside the enclosure 
should not exceed 93%. 
The average heat dissipation of the Solbrake / SMB 
depends on the Braking Torque setting and on the duty 
cycle. 
Heating inside the enclosure can be reduced through the 
use of additional ventilation. 

Note: 

The heat generated in the motor during braking is 

similar to the heat generated during starting. Therefore, 
high setting of the Braking Torque and/or a high duty cycle 
may require an external cooling fan for the motor. It is 
recommended to use temperature sensor in the motor 
which will allow restarting only after the motor 
temperature has reduced to an allowed level. 

Short Circuit Protection 

The Solbrake / SMB must be protected against short circuit 
by fast-acting fuses. Recommended I

t values in page 9. 

Transient Protection

 

Line transient voltages can cause malfunctioning of the 
brake and damage to the SCRs. 
When high transients are expected, an external protection 
should be used, (consult factory). 

Wiring 

Connections to L

1

, L

2

, U, V and W should be done with 

power cables. Connections to terminals 1-6 are for control 
only. 
Do not connect two Solbrake / SMB brakes in parallel as 
they are not synchronized and will be damaged. 
Mechanical and electrical interlock between Mains 
contactor C

1

 and braking contactor C

2

 must be installed to 

prevent both contactors from being closed simultaneously. 
 
 
 
 

 

 

Solbrake / SMB Wiring 

 

The Solbrake / SMB (10-17) are meant for installation on a 
Din-Rail. See options list for other Din-Rail ratings.

 

 

U V W L

1

L

2

1 2 3 4 5 6

 

 

Power Factor Capacitors 

Power factor correction capacitors must not be installed on 
the load side of the Solbrake / SMB. When required, 
capacitors should be installed on the Solbrake / SMB's line 
side. 

N

 

otes: 

1.  

The Solbrake / SMB uses Mains power to produce 
the braking torque. Therefore, a power failure or 
disconnection will disable the DC braking and the 
motor will coast to a stop without braking. 

 

2.  

When required to stop a motor during a power 
outage, an electro-mechanical brake must be used. 

 

3.  

The Solbrake / SMB cannot be used for continuous 
holding of loads, after motor had stopped. An 
electro-mechanical brake should be used for holding 
at stop position. 

 
 
 

Warning 

Wrong connections of Solbrake line and load sides 
will cause damage to the brake and motor. 

Содержание Solbrake

Страница 1: ...Solbrake SMB Electronic Motor Brake DC Injection 8 390A 220 690V I In ns st tr ru uc ct ti io on n M Ma an nu ua al l Ver 11 0 11 2002 1...

Страница 2: ...ction IP00 ATTENTION 1 This product was designed and tested for compliance with IEC947 4 2 for class A equipment 2 The Solbrake SMB brakes are designed to meet UL requirements 3 Use of the product in...

Страница 3: ...ect the brake according to the following criteria Motor Current starting conditions Motor s Full Load Ampere FLA as indicated on its nameplate even if the motor is not fully loaded The Solbrake SMB is...

Страница 4: ...tected against short circuit by fast acting fuses Recommended I2 t values in page 9 Transient Protection Line transient voltages can cause malfunctioning of the brake and damage to the SCRs When high...

Страница 5: ...commended to apply some minimal inertia on the motor shaft The Solbrake SMB incorporates the following built in time delays t1 DC Injection Brake Contactor Motor Contactor 1 2 Open t2 t3 t4 t5 1 2 Clo...

Страница 6: ...ls L1 and L2 internal contact Ca in Solbrake SMB controlling motor contactor closes after Mains voltage is connected and terminal 1 2 are open When operating in Manual mode DC injection will stop afte...

Страница 7: ...L C1 C2 SMB Control M L1 L2 U V W C2 O L 1 2 SMB Power 3 4 5 6 Ca Cb C2 1 Cr 2 Stop O L Cf C2 SMB Control Start Forward Cf 2 Cr 1 Cf 1 Cr 3 Cf 4 Cr Start Reverse Cf 3 Cr 4 Cf Cr Reversing C2 SMB Cont...

Страница 8: ...g has ceased and motor is still turning increase braking Torque setting and try again b If motor has stopped and the Yellow LED remains on decrease Braking Time setting until the Yellow LED turns off...

Страница 9: ...C 000 BS 88 180 C330144 H600399 Solbrake SMB 105 100000 GSGB350 500V 350A 6 6 URD 2x000 BS 88 355 V330160 H600399 Solbrake SMB 210 600000 GSGB580 500V 710A 6 6 URD 31 D 11 0630 Q300026 D600188 Solbrak...

Страница 10: ...Technical Specification Solbrake 17A 105 90 105 75 6 5 4 3 2 1 L2 L1 W V U Solbrake 31 58A 10...

Страница 11: ...Technical Specification Solbrake 105 210A 77 12 20 17 12 12 M6 W L1 L2 U V 280 263 160 Solbrake 310 390A V 63 4 L W V 222 224 W L 384 18 18 L U U L 11...

Страница 12: ...2 10 sec Optionally 1 30 sec Protection Automatic stopped motor sensor Switches off the DC injection automatically when motor has come to a complete stop Indications ON Green Illuminates when power is...

Отзывы: