Troubleshooting

Troubleshooting

66

FWunmatched

Firmware Version Fault

 Check if the ARM version is matched.

 Or seek help from us, if can not go back to normal state.

Inter Com Fault

BatPowerLow

Internal Communication Fault

 Or seek help from us, if can not go back to normal state.

 Turn off the PV, battery and grid , reconnect them.

EPS Battery Power Low

 Or seek help from us, if can not go back to normal state.

 Charge the battery.

DSP System Fault

PhaseAngleFault

System Fault

 Seek help from us, if can not go back to normal state.

Phase Angle Fault

 Or seek help from us, if can not go back to normal state.

 Please check whether the AC connection is correct.

AC HC T  Fault

Parallel Fault

AC Current Sensor Fault

 Or seek help from us, if can not go back to normal state.

 Turn off the PV, battery and grid , reconnect them.

PLL_OverTime Fault

 Or seek help from us, if can not go back to normal state.

 Please check whether the AC connection is correct.

Inv EEPROM  Fault

PLL_OverTime Fault

Inverter EEPROM Fault

 Or seek help from us, if can not go back to normal state.

 Turn off the PV, battery and grid , reconnect them.

Parallel Fault

 Or seek help from us, if can not go back to normal state.

 Parallel system has two or more master machine.

RCD Fault

Residual Current Device Fault 

 Check the impedance of DC input and AC output.

 Disconnect PV+ , PV- and battery, reconnect them.

 Or seek help from us, if can not go back to normal state.

EPS Relay Fault

EPS Relay Fault

 Disconnect PV+ , PV- , grid and battery, reconnect them.

 Or seek help from us, if can not go back to normal state.

Grid Relay Fault

EPS Relay Fault

 Disconnect PV+ , PV- , grid and battery, reconnect them.

 Or seek help from us, if can not go back to normal state.

BatRelayFault

Other Devide Fault

 Disconnect PV+ , PV- , grid and battery, reconnect them.

 Or seek help from us, if can not go back to normal state.

BMS_External_Err

Battery Fault-extarnal fault

 Please contact battery suppiler.

BMS_Internal_Err

Battery Fault-intarnal fault

 Please contact battery suppiler.

BMS_TemHigh

Battery Fault-over-temperature fault

 Please contact battery suppiler.

BMS_CellImblance

Battery Fault-cell imbalance fault

 Please contact battery suppiler.

Meter Fault

DSPunmatched

Meter Fault.

 Please check if the meter is in normal working.

 Or seek for help from us if can not back to normal.

DSP Version Fault.

 Please check if the DSP1 version is matched.

 Or seek for help from us if can not back to normal.

BMS_TemLow

Battery Fault-under-temperature fault

 Please contact battery suppiler.

Mgr EEPROM Fault

Manager EEPROM Fault.

 Turn off the PV, battery and grid , reconnect them.

 Or seek for help from us if can not back to normal.

● 

If your inverter's information panel is not displaying a Fault light, check the 

following list to make sure that the present state of the installation allows 
proper operation of the unit.

— Is the inverter located in a clean, dry, adequately ventilated place?
— Have the DC input breakers been opened? 
— Are the cables adequately sized and short enough?
— Are the input and output connections and wiring in good condition?
— Are the configurations settings correct for your particular installation?
— Are the display panel and the communications cable properly  
     connected and undamaged?

Contact SolaX Customer Service for further assistance. Please be prepared to 
describe details of your system installation and provide model and serial number 
of the unit.

67

 Turn off  high power device , press “ESC”  to restart the inverter.

 

 normal.

The system will back to normal if the grid is

 

 normal.

The system will back to normal if the grid is

 The DSP1 version is different.

BMS_OverVoltage

Battery Fault-overvoltage fault

 Please contact battery suppiler.

BMS_LowerVoltage

Battery Fault-undervoltage fault

 Please contact battery suppiler.

BMS_ChargeOCP

Battery Fault-charge overcurrent fault

 Please contact battery suppiler.

BMS_DischargeOCP

Battery Fault-discharge overcurrent fault

 Please contact battery suppiler.

Содержание X3-Hybrid

Страница 1: ...tware etc and no reproduction or distribution of it in any form or by any means All rights reserved SolaX Power Co Ltd reserves the right of final interpretation No 288 Shizhu Road Tonglu Economic Dev...

Страница 2: ...Important Safety Instructions 2 2 Explanation of Symbols 2 3 CE Directives 3 Introduction 3 1 Basic Features Modes 3 2 Work 3 3 Dimension 3 4 Terminals of PV Inverter 4 Technical Data 4 6 General Data...

Страница 3: ...a hazardous situation which if not avoided could result in death or serious injury 03 8 Setting 8 1 Control Panel 8 2 Menu Structure 8 3 LCD Operation 9 Troubleshooting 9 1 Trouble Shooting 9 2 Routi...

Страница 4: ...ure that existing wiring is in good condition and that wire is not undersized Do not disassemble any parts of inverter which are not mentioned in installation guide It contains no user serviceable par...

Страница 5: ...inals is typically more than 30 volts Lightning will cause a damage either from a direct strike or from surges due to a nearby strike Anti Islanding Effect Islanding effect is a special phenomenon tha...

Страница 6: ...e may occur to the unit Read this instructions before you work on the unit If you are unable to understand the dangers warnings cautions or instructions please contact an authorized service dealer bef...

Страница 7: ...ng under EPS mode otherwise the inverter will shutdown with an overload fault warning Please confirm with the mains grid operator whether there is any special regulations for grid connection Digram A...

Страница 8: ...e Priority battery load grid when charging Priority load battery grid when discharging This mode applies the area that has electricity price between peak and valley User can use off peak electricity t...

Страница 9: ...Hybrid 8 0 D X3 Hybrid 8 0 N X3 Hybrid 10 0 D X3 Hybrid 10 0 N A 4000 B 4000 1000 720 200 950 280 800 11 11 14 14 180 300 2 A 1 B 1 A 5000 B 5000 1000 720 200 950 370 800 11 11 14 14 180 300 2 A 1 B...

Страница 10: ...Technical Data X3 Hybrid 5 0 D X3 Hybrid 5 0 N X3 Hybrid 6 0 D X3 Hybrid 6 0 N X3 Hybrid 8 0 D X3 Hybrid 8 0 N X3 Hybrid 10 0 D X3 Hybrid 10 0 N 5000 5000 7 2 10000 60s 6000 6000 8 7 12000 60s 8000 80...

Страница 11: ...reas Not in the cool air directly Not near the television antenna or antenna cable Not higher than altitude of about 2000m above sea level Not in environment of precipitation or humidity 95 Under good...

Страница 12: ...sion tubes in the holes and tighten them Then install the wall bracket with the expansion screws Installation tools crimping pliers for binding post and RJ 45 screwdriver manual wrench and Step 1 Step...

Страница 13: ...h input area Same type Same quantity Identical alignment Identical tilt Please do not make PV positive or negative ground In order to save cable and reduce the DC loss we suggest to install the invert...

Страница 14: ...ial sectional area 3 3 Remove 12mm of insulation from the end of wire 3 4 Insert stripped wires into AC terminal and insure all conductor strands are captured in the AC terminal 3 5 Compress the AC te...

Страница 15: ...ion guide above espescially for the wiring of neutral line grounding and RCD please contact us before any operation Electrical Connection Electrical Connection 26 27 EPS wiring diagram The below diagr...

Страница 16: ...re it is within the EPS output power range then turn the inverter back on For the nonlinear load please make sure the inrush power should be within the EPS output power range WARNING Below table shows...

Страница 17: ...ug and positive cable for DC socket are live Hold the housing on the screw connection Step3 Press down spring until it clicks audibly into place it must be possible to see the fine wire strands in the...

Страница 18: ...n addtionally earth the inverter to the enclosure of a second earthing or equipotential bonding if it is required by local safety This prevents electric shock if the original protective conductor fail...

Страница 19: ...the communication wires then insert one side of wires into connector ports Step4 Insert connector into Meter terminal inside of the inverter Insert the other side of wires into corresponding meter po...

Страница 20: ...e can still be connected when using LAN connection Could Router data cable 6 8 DRM Connection DRM is provided to support several demand response modes by emitting control signals as below DRM Connecti...

Страница 21: ...of the inverter Step2 Build the connection between the inverter and router 6 10 RF Connection optional X3 Hybrid inverter provides a RF radio frequency interface which control the switch time of a des...

Страница 22: ...nly required for inverters which are commissioned in Italy The Italian standard requires that all inverters feeding into the utility grid are equipped with a self test function in accordance with CEI...

Страница 23: ...n accordance with above form strictly Do not modify the program file name or it may cause the inverter is fail to upgrade Step2 Turn off the DC switch AC breaker EPS breaker and battery Then unscrew t...

Страница 24: ...er with the installer password Grid Service PhasePowerBalance Indicator LED Function Button Down button Move cursor to downside or decrease value ESC button Return from current interface or function O...

Страница 25: ...time The information of the interface is as below Power means the instant output power Today means the power generated within the day Battery means the left capacity of battery energy Power 0W Today 0...

Страница 26: ...s voltage current power EPS PaS 2300VA Ua 230 0V Ia 10 0A Pa 2260W History Inverter Yield Charger Yield EPS Yield Load Consume System RunTime Feed in Energy Error Logs History Inverter Yield Charger Y...

Страница 27: ...Load Factory Reset Config Guide Work Mode Relay Control New Password Reset Errorlog Setting This function is used for setting of the inverter time connection battery grid and so on Enduser can set Dat...

Страница 28: ...t Advanced d 1 1 Safety User can set safety standard according to different countries and grid tied stanndards There are 8 standards to select May change without notice Item 7 1 2 3 4 5 6 8 Country VD...

Страница 29: ...Grid The enduser do not need to set the grid parameters All default value has set on factory according to safety rules If need to reset any changes should according to the requirement of local grid Pa...

Страница 30: ...rid is balanced Select Disable means the three phase output power from inverter is balanced and it is the default value Function Control Disable Phase Power Balance d 1 7 Grid Service Grid Service can...

Страница 31: ...nverter with E Version can work on the EPS mode EPS parameters can be set as below Mute means you can set the warning of system which has entered EPS mode No means there will be a buzzing and it is th...

Страница 32: ...rmally This work mode applies to the area where suffering from blackout regularly The priority of inverter output power is supplying the load feeding to the grid charging the battery This work mode ap...

Страница 33: ...tch can be selected from ON or OFF ON means the inverter is on working condition and it is inverter default status OFF means the inverter stop delivering all power but the LCD remains on Switch ON Sys...

Страница 34: ...attery input voltage is within the normal range Or seek help from us AC10M Volt Fault The grid voltage is out of range for the last 10 Minutes The system will back to normal if the grid is back Or see...

Страница 35: ...ult extarnal fault Please contact battery suppiler BMS_Internal_Err Battery Fault intarnal fault Please contact battery suppiler BMS_TemHigh Battery Fault over temperature fault Please contact battery...

Страница 36: ...least every 12 mouths please contact manufacturer to arrange qualified person who has adequate training kownledge and practical experience to perform these tests Please kindly noted this action is not...

Страница 37: ......

Отзывы: