4.1 Starting up a new installation: 

(See illustration on page 10 for references) 
 

 

1. 

Check that all connections are joined correctly and  

2. 

ensure that the pump (12V) is disconnected  

3. 

Fully open valves V4 an V5, V1 must be closed 

4. 

Water (without anti-freeze) is filled via valve V2 until water reaches the expansion tank 

5. 

Shut valve V2 and add water to via valve V3 until the water reaches the expansion tank 

6. 

Check if there are any leakages and open V1, shut V3 and let the air out by the red handle. 

 

 
4.2 Testing pump and circulation  
 

1. 

Connect the pump (take care to use correct polarity!)  

2. 

If the sun does not shine a 12V battery may be used to run the pump the yellow remark below on this page. 

3. 

Check the flow gauge when the pump runs. Output should be at least 1 L/min 

4. 

If the flow is below this minimum there is probably air in the system. 

5. 

A power drill pump may be inserted between valves V3 and V2 (V1 must then be closed) to force circulation. 

6. 

The pump sucks from valve V3 and blows into valve V2 

7. 

Run for some minutes until there is no evidence of air bubbling in the expansion tank. 

8. 

Test the system again with the ordinary pump 

9. 

Add water if the liquid level in the expansion tank is below minimum 

10. 

If there is flow in the system proceed to 4.3 Otherwise go back to step 5 

 

 
4.3 Adding anti-freeze (for locations with risk of frost) 
 

1. 

4,5 L of water mixed with anti-freeze (fluid) is pumped in at valve V2  

2. 

An equivalent volume is let out at valve V3 

3. 

Watch the liquid level in the expansion tank 

4. 

If the level is below minimum add water. When doing this turn off the pump to avoid any sucking in of additio-
nal air. 

5. 

Do not fill the expansion tank to overflowing.  

 

4.4 Re-starting your SV30AWX 
 

If you have turned off the fluid based part of your SV30AWX for a period, it is necessary to re-start it.  
Whilst the equipment is already filled with liquid, this will normally cause no problem.  
Please follow the instructions below: 
 

• 

Check the liquid level in the expansion tank. Add water if it is below minimum 

• 

Connect the pump 

• 

If there is sunlight, the circulation will normally start 

• 

Otherwise follow the instructions given above in 4.2. step 5 

Note:  If a battery is used as starting aid, the regulator should be bypassed and a 12V battery  
connected direct to the pump. As long as you do this you may use the highest speed level on  
the pump - step 5. This will normally enable the pump to push all air out of the collector and 
tubing. When finished set back the speed level at 1 or 2. Be sure that the flow is 1 litre pr minute  
or more.  

Содержание SV30AWX

Страница 1: ...System for Fresh Air and Domestic Hot Water with 12V Solar Cell Operated Pump and Fan See separate instructions for wall or roof mounting of the standard SV30 These manuals also describe the regulator unit and air heating system July 2011HJC SolarVenti at your sunny service ...

Страница 2: ...ion tank 9 3 5 Installing the hot water cylinder 10 3 5 1 Fittings on the hot water cylinder 10 3 5 2 Mounting the fittings on the hot water cylinder 11 3 5 3 Connecting the domestic water 12 4 0 The SV30AWX in operation 12 4 1 Starting up a new installation 13 4 2 Testing pump and circulation 13 4 3 Adding anti freeze for locations in risk of frost 13 4 4 Re starting your SV30AWX 13 5 0 Venting t...

Страница 3: ...technical information concerning specific components in the system Separate instructions are provided for roof or wall mounting the collector When mounting on roof however it is important to distinguish between the two types available Type 1 for solid roofs with profiled sheeting for instance fibre cement Type 2 for steel plate or asphalt roofing Upon receipt of your SV30AWX please check that you ...

Страница 4: ...r house pleasantly dry and moderately heated most of the year Domestic hot water often as a supplement to a pre installed electric water heater 1 1 The SV30AWX Principle Flow meter Hot water cylinder supplying 100 l domestic hot water SV30AWX solar collector 12 v solar cells for fan and pump Cold water in Hot water out Warm air into the house 12V Pump Valve Valve Valve 12 v Regulator ...

Страница 5: ...side with the solar cell at the highest position Inlet and outlet are always placed on the same side of the collector By rotating the collector 180º you may choose between the right and the left side 1 2 A roof mounted SV30AWX solar collector Max 45 degrees 5 Tubing and expansion unit is placed behind the solar cell ...

Страница 6: ... collector above or against a room well suited for this purpose Please read separate instructions for further details 2 2 How to position the hot water cylinder The hot water cylinder should be installed so that the horizontal distance to the SV30AWX solar collector is as short as possible The hot water cylinder can often be located in a scullery or a furnace room or wherever practical However the...

Страница 7: ...be tween the expansion tank and the cylinder as the pump pressure is released behind the expansion tank SolarVenti SV30AWX system principal drawing Patented air and fluid collector HJC June 2011 Patented collector Europe EP 1448937 Incl Eurasia Japan 3808466 China 02823485 5 Australia 2002350429 USA US 7 694 672 B2 Canada 2 467 078 3000 mm 1020 Area 1 for copper absorber Udgang fra absorber A A Vi...

Страница 8: ...ll secure the watertight lead in of the 16 mm tube through the roof plate 3 2 Piping and Insulation 1 16 mm tube smooth tube for distances over 12 m is insulated and fixed Fasten the tubes with strips or wire to laths at short invervals to avoid bends 2 Intense heating may result in linear expansion especially in rib tubes but smooth tubes will also expand to some degree Normally this causes no pr...

Страница 9: ...ot water cylinder Air inlet and outleton top of expansion tank Normal level of fluid Max level of fluid Minimum level of fluid Be carefull not to overfill the tank extra fluid may be filled in here Clear tube to control fluid level Hide under the collector when not in use Put a lid on top of this tube with a tiny hole for the air The expansion unit has several purposes 1 to absorb the expansion of...

Страница 10: ...he temperature rises in the cylinder due to the expansion of hot water Therefore it must be con nected to a drain Important Note the marking for flow direction on the pump and be sure to fit it in a vertical position so that it can self ventilate Hot supply line To the bottom of the solar collector 12 V pump with 5 speed steps Piping with 16 mm PP tubes Expansion tank Flow meter Tube stubs are fit...

Страница 11: ...the union nut only manual power O ring Clamp ring Union nut EV brass collector use the same principle as for the plastic collector Take care that the clamp ring is straight and pressing against the O ring 3 5 2 Mounting the fittings on the hot water cylinder Piping arrangements may differ slightly from the example shown on the pictures When the hot water cylinder has been installed and is leveled ...

Страница 12: ...pp 0 5 L at normal level Totalling approx 4 5 L Now you are ready to fill the solar collector circuit with water using the steps stated on the next page Hot water cylinder with 100 L domestic water From solar collector To solar collector Hot or preheated water out The cold water inlet is connected to the 3 4 stub for cold water in pos c The hot water outlet is connected to the 3 4 stub for hot wat...

Страница 13: ...level in the expansion tank is below minimum 10 If there is flow in the system proceed to 4 3 Otherwise go back to step 5 4 3 Adding anti freeze for locations with risk of frost 1 4 5 L of water mixed with anti freeze fluid is pumped in at valve V2 2 An equivalent volume is let out at valve V3 3 Watch the liquid level in the expansion tank 4 If the level is below minimum add water When doing this ...

Страница 14: ... sunny day 6 1 Adjustment of the flow in the solar collector Make sure that the system is well vented for instance by running the pump for a couple of hours see page 13 At low speed the flow should be minimum 1 0 L min The velocity varies according to the amount of sunlight The flow is indicated at the very back of the white marking Normally the flow is higher than 1 0 L min which is perfectly OK ...

Страница 15: ... when not staying in the house and need as much warm fresh air as possible The plant will perform at its maximum total kW when both pump and fan run simultaneously In good sunlight the so lar cell may run 2 3 fans together with the pump 8 0 Maintenance Responsibility for the maintenance of the equipment rests with the user An annual service check is recommended The SV30AWX requires a minimum amoun...

Отзывы: