38

off 

 button for three seconds to save and exit. Afterwards, the unit 

will continue to operate normally.

Adaptive Start feature

This feature can only be used for the weekly program. When the unit 

is set to automatic power-on without this setting, it switches on at the 

designated time and provides heating. However, it will take some 

time for the unit to reach the designated temperature. This causes 

inconvenience for the user due to the delay in heating. The adaptive 

start feature is designed to prevent this. If this feature is activated, 

your unit will start heating at a time depending on the difference 

between the ambient temperature and the desired temperature when 

the designated automatic power-on time is close. This feature ensures 

that the ambient temperature is at the desired temperature at the 

designated time. (The Adaptive Start Feature does not guarantee 

that the ambient temperature will be exactly at the designated 

temperature at the time set for the program. Because the environment 

in which the device is placed has many factors that make heating 

difficult in practice such as thermal insulation, doors and windows 

left open, a very large volume, and heat leakage.) 

The instructions below must be followed in order for this feature to 

work with maximum efficiency:

1. Selecting the power according to the space where the unit is placed, 

2. Keeping the doors and windows closed and preventing other leaks, 

if any. 3. Ensuring thermal insulation in the environment where the 

unit is placed, 4. Setting the adaptive start parameters accurately. 

Default values: “P 01” : 20 min and “P 02”: 5 hours. At least one of 

these parameters must be set to 0 to deactivate this feature.

Adaptive Start parameters

This feature has two parameters. The first parameter is the duration 

for early automatic power-on per degree. (This value is set with the 

parameter “P 01”.) This duration is measured in minutes. It can be 

set from 0 to 40 minutes. The unit calculates how early it should 

start heating by multiplying this parameter value by the difference 

between the current ambient temperature and the target temperature. 

For example, if the unit is set to switch on at 09.00 at 23 degrees 

Celsius in the weekly program, if the ambient temperature is 19 

degrees Celsius and if the parameter is set to 20 minutes per degree 

Celsius, the time for the unit to start heating is calculated using the 

following formula: 

Heating Time = Program Time - (Target Temperature - Current 

Temperature) x Parameter Value = 09:00 – (23 – 19) x 20 

= 09:00 – 80 min. (1 hour 20 min.) The time to start heating = 07:40.  

So, the unit starts to heat 80 minutes (1 hour 20 minutes) earlier than 

the designated time.

If the unit is on, if the adaptive start feature is activated and if the unit 

switches on earlier to start heating, “A 23” will appear on the display 

when you press and hold the plus 

 or minus   button for three 

seconds. The number 23 represents the target temperature value that 

you set and it will display your designated temperature. 

If the plus   or minus 

 button is pressed while the adaptive start 

is deactivated, the unit will only display “23”.

The other parameter is to set a limit for the early automatic power-on 

time. Even if the early power-on time calculated above exceeds this 

parameter value, the unit will not start heating before the time set 

with this parameter. (This value is set with the parameter “P 02”.) 

This parameter is measured in hours. It can be set from 0 to 5 hours.

Adaptive Start parameter Setting 

(“p 01” and “p 02”)

Switch off the heater using the power switch on the side. Switch on 

the heater while pressing and holding the menu button  “ASEt” 

appears on the heater’s display for approximately six seconds. “P 01” 

will start flashing on the display. The plus 

 and minus   buttons 

can be used to switch to the other parameter (“P 02”). Press the 

menu button   to change the value of the desired parameter. The 

parameter value will appear on the display, and the desired value can 

be set using the plus   and minus   buttons. If you press the menu 

button   again, you can change the parameter again. Press and hold 

the on/off button   for three seconds to save your settings and exit. 

Afterwards the unit will continue to operate normally.

Содержание KIP4550E10

Страница 1: ...MANUALULUTILIZATORULUI Solaris este marc nregistrat a Masta Company KIP4550M10 KIP4570M20 KIP4550E10 KIP4570E20 KIP4550P10 KIP4570P20 www mastas com CONVECTOR ELECTR C Din...

Страница 2: ...cte cum ar fi distan a de gard la sol distan a de la fereastr sau u dimensiunea camerei sau de fluxurile de circula ie a c ldurii n interiorul camerei Luminozitatea afi ajului digital scade automat no...

Страница 3: ...l p stra i ca surs de referin pentru a utiliza acest produs n cel mai eficient mod Acesta este produs n fabricile noastre moderne n conformitate cu principiile de calitate social 4 V rug m s apela i...

Страница 4: ...pania noastra nu va fi considerata responsabila pentru daunele cauzate de utilizare fara aplicarea impamantarii Ac iona i ntotdeauna convectorul n pozi ie vertical nainte de utilizare citi i instruc i...

Страница 5: ...tinge fi a Acest aparat nu este prev zut pentru utilizarea de c tre persoane copii inclusiv cu capacitate fizic senzitiv sau mental redus cu lips de cuno tin e i experien cu excep ia cazului n care au...

Страница 6: ...te de a muta convectorul Utilizarea dispozitivului respect regulile de securitate la incendiu prev zute de legisla ia n vigoare Nu folosi i convectorul n apropierea unui du b i sau piscine Se recomand...

Страница 7: ...ponente dun toare s n t ii omului nc lzitoarele Convectoare Electrice se gsesc n felul de trei 3 modele diferite manuale digitale i profesionale 1 Corp convector 2 Panoul frontal 3 Termostat i comutat...

Страница 8: ...24 IP 24 IP 24 IP 24 Termostat mpotriva c ldurii excesive disponibil disponibil disponibil disponibil disponibil disponibil Control mecanic termostat disponibil disponibil Afi aj consum de energie di...

Страница 9: ...2 Ne2 G F F Faz N N tr Te Emniyet Termostad Tm Manuel Kontroll Termostat K A ma Kapama Tu lu Anahtar SO Devrilme Anahtar R Rezistans KIP 4550 Manuel 1000Watt Elektrik Devre emas SO Te Tm K R Ne Fig 2...

Страница 10: ...ioar a suportului la minim 100 mm sau max 200 mm Marca i g urile pentru urub prin orificii cu ajutorul unui creion pix Trebuie s ave i grij s v asigura i c zonele de siguran sunt p strate libere pentr...

Страница 11: ...pe perete va fi tras i introdus prin g urile de pe partea superioar a convectorului pentru a fixa unitatea Not Dac dori i s dezinstala i convectorul trebuie s trage i de c rligele superioare i s l apl...

Страница 12: ...i introduce i cap tul metalic al piciorului de plastic n orificiu 1 de sub nc lzitor i fixa i piciorul rotindu l n direc ia s ge ii 2 a a cum se arat n figura A Picioarele de plastic vor fi fixate sub...

Страница 13: ...Func ioneaz la 1000 de wa i c nd se deschide ntr o singur etap i la 2000 de wa i c nd se deschide n dou etape Dispozitivul de 1000 wa i are un singur comutator de alimentare Cre terea sau reducerea te...

Страница 14: ...De exemplu p r si i casa i dori i ca aparatul s porneasc nainte de a veni acas n acest caz fi a trebuie s fie b gat n priz iar ntrerup torul de alimentare a se vedea figura l trebuie s fie pornit iar...

Страница 15: ...2 3 secunde n timp ce aparatul func ioneaz cuv ntul LO prescurtare pentru LOCK va fi afi at pe ecran Butoanele de pe panoul de control nu vor func iona dac sunt ap sate dup ce efectua i aceast setare...

Страница 16: ...u ore 03 sau 33 Timp de func ionare a rezisten ei or Acelea i taste de pe Panoul de control au acelea i func ii Utilizarea este aceea i Modelul profesional are dou op iuni de programare diferite difer...

Страница 17: ...uit valoarea prin operare manual Dac nu se dore te utilizarea programului s pt m nal trebuie s se treac la modul de programare zilnic Setare programare s pt m nal Dispozitivul este oprit la comutatoru...

Страница 18: ...u aceast valoare a parametrului dispozitivul calculeaz la ce perioad de timp n urm ar trebui s nceap nc lzirea De exemplu se las dispozitivul s func ioneze la 23 de grade la ora 09 00 n programul s pt...

Страница 19: ...Unitatea este acoperit n ntregime de garan ia Companiei noastre toate piesele inclusiv 3 Daunele produse de modurile de utilizare nespecificate n manualul utilizatorului nu sunt acoperite de garan ie...

Страница 20: ...his sau nchis Vezi Fig 1 5 n cazul n care aparatul nu func ioneaz c nd men ine i butonul ap sat pentru cca 2 3 secunde de i sunt ndeplinite toate condi iile de mai sus v rug m s contacta i distribuito...

Страница 21: ...USER MANUAL since Solaris by Masta KIP4550M10 KIP4570M20 KIP4550E10 KIP4570E20 KIP4550P10 KIP4570P20 www mastas com ELECTR c CONVECTOR HEATER...

Страница 22: ...d clearance distance window or door distances the size of the room or by the heat circulation streams inside the room Digital display brightness decreases automatically at night SAFETY INSTRUCTIONS 24...

Страница 23: ...uctions in this manual completely before using this unit and keep it as a reference source in order to use this product in the most efficient way which is produced in our modern facilities in accordan...

Страница 24: ...e damages caused due to use without the application of grounding Always operate heater in an upright position Before operating read montage instructions carefully Always check heater for black glass m...

Страница 25: ...ended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning u...

Страница 26: ...ted by current legislation Do not use the heater in reach of a shower bath or a swimming pool It is recommended that you do not use your heater in smoky and dusty areas It is recommended that you clea...

Страница 27: ...aters contains no chemicals harmful to human health The Electric Convectors are offered in three different models Manual Digital and Professional 1 Body 2 Front Panel 3 Thermostat and Adjustment Knob...

Страница 28: ...pill IP IP 24 IP 24 IP 24 IP 24 IP 24 IP 24 ThermostatAgainstExcessiveHeat Disponible Disponible Disponible Disponible Disponible Disponible MechanicalThermostat Control Disponible Disponible Power Co...

Страница 29: ...Ne1 Neon Lamba 1 Ne2 Neon Lamba 2 G Toprak KIP 4570 Manuel 2000Watt Elektrik Devre emas SO Te Tm K1 R 1 Ne1 K2 R 2 Ne2 G F F Faz N N tr Te Emniyet Termostad Tm Manuel Kontroll Termostat K A ma Kapama...

Страница 30: ...e floor and the lower part of the bracket as min 100 mm or max 200 mm Mark the screw holes through the holes with an appropriate pen You have to be careful to ensure the safety zones are kept free in...

Страница 31: ...Figure 11 Dimensions of the convector after assembly Figure 9 Attaching upper hook of the wall mounting brackets to the convector Figure 10 Back view of fastening the upper 6 The spring section on th...

Страница 32: ...r upside down and insert the tab on the plastic leg to the slot 1 under the heater and fix the leg by turning it in the direction of the arrow 2 as shown in Figure A Plastic legs will be fixed under t...

Страница 33: ...ates on 1 000 watts when the first step is switched on and 2 000 watts when the second step is switched on The 1 000 watt unit features a single power switch Increasing or reducing the temperature You...

Страница 34: ...required temperature is provided Since the new adjusted temperature will be provided within a specific period of time actual room temperature will be displayed until the requested temperature is prov...

Страница 35: ...will shine until the appliance starts to operate This light will be on until the appliance is off and the appliance will close automatically on the set time hour seen on the indicator display If you w...

Страница 36: ...r a power outage Energy Consumption Monitoring This indicates how many hours the heater s resistor has been operational To access that information press and hold the menu button for approximately six...

Страница 37: ...h to the daily program mode Weekly Program Settings Switch off the heater using the power switch on the side Switch on the heater while pressing and holding the 24 7 24 7 button hPro appears on the he...

Страница 38: ...multiplying this parameter value by the difference between the current ambient temperature and the target temperature For example if the unit is set to switch on at 09 00 at 23 degrees Celsius in the...

Страница 39: ...on recommends the following minimum indoor temperatures A minimum of 18 C or a minimum of 20 C for more vulnerable groups like children the elderly and people who are ill a minimum of 16 C in your bed...

Страница 40: ...er before making any application on the unit 4 Damages and breakdowns due to factors occurring following the delivery of the product such as transportation loading unloading storage external physical...

Страница 41: ...al or labor deficiency the repair will be made without any cost requirements under the title of labor cost replaced part cost or any other title 5 The customer may request the replacement of the unit...

Страница 42: ...No Name of The Buyer Address Model No KIP4550E10 KIP4570E20 KIP4550M10 KIP4570M20 KIP4550P10 KIP4570P20 Serial No CE Certificate Permission Date 19 08 2018 CE Certificate No 18 0902 01 Guarantee Peri...

Страница 43: ...rea produselor care nu corespund in cadrul termenului de garantie care nu sunt imputabile consumatorului se face in termen de maxim 15 zile calendaristice din momentul cand operatorul economic a luat...

Страница 44: ...10 2020 since...

Отзывы: