![SOLARFOCUS PelletElegance 10 Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/solarfocus/pelletelegance-10/pelletelegance-10_manual_1313812036.webp)
7 Hydraulic connection
8.3 Sensor resistance table
Type
KTY 81-110 PT100 PT1000 KTY 81-210
Tolerance
± 3%
± 0.7%
± 1%
± 3%
°C
Ohm
Ohm
Ohm
Ohm
-20
684
92.16
922
1367
-10
747
96.09
961
1485
0
815
100
1000
1630
10
886
103.9
1039
1772
20
961
107.79
1078
1922
25
1000
109.74
1097
2000
30
1040
111.69
1117
2080
40
1122
115.54
1155
2245
50
1209
119.4
1194
2417
60
1299
123.24
1232
2597
70
1392
127.07
1271
2785
80
1490
130.8
1309
2980
100
1696
138.5
1385
3392
120
1915
146.06
1461
3617
140
2124
153.58
1536
4186
150
2211
157.31
1573
4280
160
-
161.04
-
-
170
-
164.76
-
-
180
-
168.46
-
-
190
-
172.16
-
-
8.4 Electrical fusing
DANGER
-
There is a risk of fatal electric
shocks when working on electrical
components of the system
–
Work may be performed only by a qualified
electrician.
–
Applicable standards and regulations must
be observed.
Position of the fuses on the power element
Fuses on the power element
Rating
Size Use
F1 T 3.15A
5x20
mm
230V AC fuse: Pre-fuse main
transformer
F2 T 125mA
5x20
mm
230V AC fuse: Pre-fuse
standby transformer
F3 T 10A
5x20
mm
230V AC fuse: Relay outputs
F5 F 8A
5x20
mm
Fuse for X18 (power supply
to external modules 230V
AC)
F6 F 8A
5x20
mm
230V AC fuse: Triac outputs
F7 T 2.5A
5x20
mm
12V AC fuse: Heating
lambda sensor
F8 T 2.5A
5x20
mm
18V AC fuse: Internal elec-
tronics for main transformer
F9 T 800mA
5x20
mm
18V AC fuse: Internal elec-
tronics for standby trans-
former; display supply
F10 T 10A
5x20
mm
Spare fuse
F11 F 8A
5x20
mm
Spare fuse
F12 F 0.5A
5x20
mm
230 VAC fuse: Relay outputs
X26, X27 and X80
F13 F 0.5A
5x20
mm
Spare fuse for F12
8.5 Connecting the control to the internet
To connect the
eco
manager-
touch
boiler control to the
Internet, connect the Ethernet port
X2
(type RJ45) on
the bottom of the display by cable to a network router.
The connection is required in order to use the fol-
lowing functions:
–
mySOLARFOCUS app
–
Weatherman function
–
IP-VNC (remote access to the control)
–
Sending e-mails
i
Additional information on these functions can
be found in the operation manual.
36
Installation manual
pelletelegance