Electrical connection
38
Installation manual
octo
plus
7.2 Power supply
A separate power circuit is to be provided in the boiler room / boiler installation room for the heating system;
mains connection: 230 V AC / 50 Hz C13 A
Specification for the mains connection cable (e.g. in case of replacement): cable SIHF-J 3x1.5 mm²
7.3 Connections required for installation
Connection
Name of the component
X1
230 volt boiler plug
X3
Suction turbine
X4
Ignition device (glow pencil)
X16
Ash roller
X19
ID fan
X20
Overtemperature reset (OTR)
X23
Feed motor
X24
Motors for heat exchanger cleaning
X26
Primary supply air holding magnet
X27
Ignition supply air holding magnet
X30
Tank temperature sensor top
Connection
Name of the component
X31
Tank temperature sensor centre
X32
Tank temperature sensor bottom
X33
Feeder temperature sensor
X34
Flue gas temperature sensor
X45
Lambda sensor
X47
Speed measurement ID fan
X48
Door contact switch
X49
Filling level sensor (intermediate pellet
store)
X53
Touch display connection
7.4 Connecting the control to the internet
To connect the boiler control to the Internet, connect the Ethernet port
X2
(type RJ45) on the back of the display
to a network router via cable. The connection is required in order to use the following functions:
- mySOLARFOCUS app
- Weatherman function
- IP-VNC (remote access to the boiler control)
- Sending e-mails
7.5 Connecting the heating circuit pump (X9, X10)
Connect heating circuit pump 1 to power element connector
X9
and heating circuit pump 2 to
X10
.
If required (e.g. in the case of underfloor heating), connect a limiting thermostat.
If a limiting thermostat is not used, the contact must be bridged.
7.6 Electrical fusing
Fuses on the power element
Fuse
Rating
Size
Assignment
F1
T 3.15 A
5x20 mm
Fuse 230 V AC: Pre-fuse main transformer
F2
T 125 mA
5x20 mm
Fuse 230 V AC: Pre-fuse standby transformer
F3
T 10 A
5x20 mm
Fuse 230 V AC: Relay outputs
F5
F 8 A
5x20 mm
Fuse for X18 (power supply to external modules 230 V AC)
F6
F 8 A
5x20 mm
Fuse 230 V AC: Triac outputs
F7
T 2.5 A
5x20 mm
Fuse 12 V AC: Heating lambda sensor
F8
T 2.5 A
5x20 mm
Fuse 18 V AC: Internal electronics for main transformer
F9
T 800 mA
5x20 mm
Fuse 18 V AC: internal electronics, standby transformer; display supply
F10
T 10 A
5x20 mm
Spare fuse
F11
F 8 A
5x20 mm
Spare fuse
F12
F 0.5A
5x20 mm
230 VAC fuse: Relay outputs X26, X27 (and X80)
and X80
Relay outputs X26, X27
and X80
Relay outputs X26, X27
and X80
F13
F 0.5A
5x20 mm
Spare fuse for F12
and X80
Relay outputs X26, X27
and X80
Relay outputs X26, X27
and X80
Содержание octoplus
Страница 40: ...Initial commissioning 40 Installation manual octoplus 8 1 Commissioning log...
Страница 41: ...Initial commissioning Installation manual octoplus 41...
Страница 42: ...Initial commissioning 42 Installation manual octoplus 8 2 Customer service order form...
Страница 45: ...System schematic Installation manual octoplus 45...
Страница 46: ...System schematic 46 Installation manual octoplus...
Страница 47: ...System schematic Installation manual octoplus 47...