Chapter 3: Installation of the inverter
SolarEdge Installation Guide - MAN-01-00060-2.6
22
5
Depending on the type of inverter (single or three phase), connect the AC cable, as follows.
5
Depending on the type of inverter (single or three phase), connect the AC cable, as follows.
Login first PE wire (ground).
UPS monopha sé
UPS monopha sé
Figure 11: CA terminal of the inverter
phase
Wire Type
Connecting to the
terminal
Protective earth
PE
Line
The
Neutral
NOT
Three-phase UPS
Figure 12: AC terminal of the three-phase inverter
Wire Type
Connecting to the
terminal
Line 1
L1
line 2
L2
line 3
L3 (supplies the internal
power supply)
Protective earth
PE
Neutral
NOT
NOTE :
If the Power Control is enabled, the connection order of the lines of the grid inverter is important. A difference of 120 degree phase
between L1 to L2 and L2 to L3 between must be maintained (L1-L2-L3 and not, for example L1-L3-L2). A phase difference of 120 º between
between L1 to L2 and L2 to L3 between must be maintained (L1-L2-L3 and not, for example L1-L3-L2). A phase difference of 120 º between
between L1 to L2 and L2 to L3 between must be maintained (L1-L2-L3 and not, for example L1-L3-L2). A phase difference of 120 º between
L1 and L2, between L2-L3 should be maintained. If the network lines are not in that order, an error will be displayed on the LCD and
the inverter will not produce energy.
6
Tighten the screws of each terminal with a torque 1,2 - 1.5 N * m / 0.88 to 1.1 lb ft *.
6
Tighten the screws of each terminal with a torque 1,2 - 1.5 N * m / 0.88 to 1.1 lb ft *.
7
Check that the son are fully inserted and can be removed easily.
7
Check that the son are fully inserted and can be removed easily.
8
Tighten the gland of the AC cable with a torque of 2.8 to 3.3 N * m / 2.0 to 2.4 lb ft *.
8
Tighten the gland of the AC cable with a torque of 2.8 to 3.3 N * m / 2.0 to 2.4 lb ft *.
9
Check that there is no not connected to the inverter wire and screws are unused terminals
9
Check that there is no not connected to the inverter wire and screws are unused terminals
tight.
PE LN
L1 L2 L3 N
(EP)