Figure 24: Crimping a lug on an AC wire
Lug parameters:
Bolt hole diameter size: 10mm
Compression lugs of the one-hole, standard barrel, 600V type.
Maximum wire size: 120mm
2
(For inverter models SE50K, SE55K, SE66.6K, SE80K
use 95>mm
2
)
Maximum lug tongue thickness: 7mm
Maximum lug tongue width:
≤
33mm
5. Use heat shrink to isolate the lug barrels.
6. Remove the nut of the AC terminals.
7. Connect the lug of the AC wires according to the labels on AC terminal block. Fasten
the nut of the AC terminals with a torque of 21 N*m.
NOTE
For easy installation of the AC wires, start connecting the wires from left to
right: L1
→
L2
→
L3
→
Chapter 4: Connecting AC and PV arrays to the Synergy Manager