HEATING WITH COMBINED BOILERS
When using a combined boiler (solid and liquid
fuel), you need to press a solid liquid key
(accessory) or turn the day temperature setting
button to the minimum setting and then back after
the beep. This way you can temporarily stop the
solid fuel burner.
When the solid fuel runs out, the liquid fuel burner
is turned on automatically after a certain period of
time. If you change your mind and want to start
burning liquid fuel immediately, you can turn the
night temperature setting button to the minimum
setting and then back after the beep.
MANUAL ONE TIME TURNING ON OF D. H. W. WARMING
The function “one time turning on the d. h. w. warming” is used when you need the d. h. w.
warming outside the time program.
Activate it by turning the button to the position ON and
back to the requied temperature setting after the beep.
When the function is activated, the symbol is
shown on the display.
The controller has a special built in function that heats the water to 66 °C to prevent legion-
naries disease. You can switch on the anti-legionella program in the corresponding time
program. When the function is activated, the symbol is shown on the display.
Working thermostat on a boiler must be set on 75 – 85 °C (position 3).
ANTI-LEGIONELLA PROGRAM