INSTALLATION AND OPERATION MANUAL SolahartXXXBLK – AU
INSTALLATION AND OPERATION MANUAL SolahartXXXBLK – AU
Installation Site
Please note the following guidelines that apply to the
installation site:
•
The modules have been tested according to IEC 61215.
•
Solar modules are not explosion-proof and are not suitable
for use in explosive environments.
Ä
Do not operate solar modules near highly flammable gas
and vapors (e.g. gas tanks, gas stations).
Ä
Do not install modules in enclosed space.
Ä
Do not install modules in locations where they may be
submerged in water (e.g. floodplains).
Ä
Do not use modules as a substitute for the normal
roofing (e.g. modules are not watertight).
Ä
Do not install modules in close proximity to air conditioning
systems.
Ä
Do not install modules above 4000 m (13120 ft) altitude
above sea level.
Ä
In locations with increased salt content in the air (e.g.
close to the sea) special precautions must be taken
(see “Maintenance”).
Ä
Do not bring any chemical substance (e.g. oil, solvent etc.)
into contact with any part of the panel. Only substances,
which are released by Hanwha Q CELLS Australia Pty
Ltd, are allowed to be used during installation, operation
and maintenance.
Ä
Any installation of modules on surfaces of water is
prohibited. This includes installations on floating as
well as pile-based platforms. Hanwha Q CELLS Australia
Pty Ltd may extend the coverage of its warranty to such
installations, based on a case by case assessment of
the system design and location. A prior written consent
by the warrantor is required in any case.
The solar modules are designed for the following applica-
tions:
•
Operating temperatures from –40 °C to +85 °C
(–40 °F to +185 °F).
•
Pull loads up to max. 4000 Pa and push loads up to
max. 5400 Pa (see chapter 2.3 mounting options).
•
Installation using a mounting frame for solar modules.
Prevention of Shadowing Effects
Optimal solar irradiation leads to maximum energy output:
Ä
For this reason, install the modules so that they face
the sun.
Ä
Avoid shadowing (due to objects such as buildings,
chimneys or trees).
Ä
Avoid partial shading (for example through overhead
lines, dirt, snow).
Mounting Structure Requirements
The Modules shall be installed and operated on mounting
frames that comply with any applicable laws and stipula-
tions as well as with the following:
•
Conform to the necessary structural requirements.
•
Compliant with local snow and wind loads.
•
Properly fastened to the ground, the roof, or the façade.
•
Forces acting on the module are relayed to the mounting
substructure.
•
Ensures sufficient rear ventilation of the module.
•
Guarantees long-term stability.
•
Avoid the usage of different metals to prevent contact
corrosion.
•
Allows for stress-free expansion and contraction due to
temperature fluctuations.
Ä
Ensure that no mechanical stresses (e.g., caused by vibra-
tions, twisting, or expansion) applied to on the module.
Ä
Ensure that the clamps and the mounting frame are
compatible.
Clamp System Requirements
Use customary clamps that satisfy the following require-
ments:
•
Clamp width:
≥
40 mm.
•
Clamp height compliant with a 32 mm frame height.
•
Clamp depth: 7-12 mm (applicable for all CL clamping
mounting options at section 2.3 Mounting options).
•
Clamps are not in contact with the front glass.
•
Clamps do not deform the frame.
•
Clamps that satisfy the structural requirements of the
installation site.
•
Long-term stable clamps that securely affix the module
to the mounting frame.
Module Orientation Requirements
•
Vertical or horizontal installation is permitted.
Ä
Ensure that rain and melting snow can run off freely.
No water accumulation.
Ä
Ensure that the drainage holes in the frame are not
covered. No sealing.
Ä
Maintain the permissible angle of
inclination.
•
Minimum angle of inclination: 3°
•
Maximum angle of inclination: 75°
75°
3°
2.2 Requirements
2 PLANNING
Fig. 2:
Installation options for crystalline Solahart modules. All dimensions are given in mm. Also observe the
allowed static loads and clamping range as specified on the following page.
The illustrated installation options apply for both horizontal and vertical module orientation.
Module
Clamp
Subconstruction
Mounting profile
2.3 Mounting options
2 PLANNING
TYPE OF
INSTALLATION
MODULE
POINT MOUNTING SYSTEM
LINEAR MOUNTING SYSTEM
INSTALLATION
WITH CLAMPS
Solahart300BLK
Solahart305BLK
Solahart310BLK
Solahart315BLK
HYBRID
CLAMPING
Solahart300BLK
Solahart305BLK
Solahart310BLK
Solahart315BLK
INSTALLATION
ON MOUNTING
POINTS
Solahart300BLK
Solahart305BLK
Solahart310BLK
Solahart315BLK
INSTALLATION
WITH INSERTION
PROFILES
Solahart300BLK
Solahart305BLK
Solahart310BLK
Solahart315BLK
NOT PERMITTED
300 - 400
EUROPE
0 - 250
CL5
CL2a
0 - 250
CL2b
0 - 250
0 - 300
CL2a
0 - 300
CL2b
CL2a
0 - 200
CL2b
0 - 200
IP1
IP2
IP1
IP2
IP1
IP2
IP1
IP2
CL2a
0 - 250
CL2b
0 - 250
0 - 300
CL2a
0 - 300
CL2b
CL2a
0 - 200
CL2b
0 - 200
345
274
FB2
EN
4 × Mounting
points
4 × Mounting
points
FB2
EN
345
4 x Mounting
points
274
4 x Mounting
points
FB1
FB1
CL1
0 - 250
250 - 450
450 - 550
0 - 200
200 - 350
350 - 450
EUROPE
ASIA
CL1
CL3
CL4
250 - 450
200 - 350
0 - 300
0 - 300
CL3
CL4
CL4
0 - 200
ROW