ups 325
Specifications
Line Transient Protection: Passes ANSI/IEEE C62.41 Category A testing.
Safety Compliance: TUV/GS Listed, AS3260
EMC Compliance: CISPR 22 Class B, Vfg 243-91/46-92 B, EN55022, CE Mark Self-certified to: CE
Marking Directive 93/68/EEC, Low Voltage Directive 73/23/EEC, C-Tick, AS3548.
Noise (RF) Suppression: Full-time EMI/RFI filtering.
Efficiency: > 95% on line
Capacity VA/Watts: 400VA / 250W; 750VA / 470W; 1000VA / 630W
Voltage Nominal: (A Model): 240 VAC
Voltage Range: (A Model): 0 - 300 VAC, operating on battery and buck/boost, 197 - 283 VAC without
battery discharge.
Frequency: 50/60 Hz auto-sensing 57 - 63 Hz (60 Hz); 47 - 53 Hz (50 Hz) (50/60 Hz ± 0.5 Hz on battery.)
Minimum Runtime (minutes): 400VA Model: Full load: 4.5 minutes. Half load: 17 minutes.
750VA Model: Full load: 4.5 minutes. Half load: 17 minutes.
1000VA Model: Full load: 4.5 minutes. Half load: 15 minutes.
Transfer Time: 2-6 ms typical.
Battery: Sealed, maintenance-free, valve-regulated, UL 924 recognized.
400 VA Models: One 12 V, 9.0 AH batteries.Nominal Voltage is 12 VDC.
750 VA Models: Two 12 V 7.0/7.2 AH batteries. Nominal Voltage is 24 VDC.
1000 VA Models: Three 6 V 12.0 AH batteries. Nominal Voltage is 18 VDC.
Automatic Battery Test: Automatic battery test occurs upon startup and every 14 days thereafter. Alarm
will sound if the battery fails this test.
Battery Recharge Time (to 95% of capacity): 400VA, 750VA and 1000VA: 8 hours. Recharge time is
lowered with reduced load.
Overcurrent Protection (on line): All Models: Fused and Circuit Breaker.
Input Fault Current (maximum): All Models: 15A.
AC input Plug/Cord Information: 400VA: CEE 22 recessed plug
750VA: CEE 22 recessed plug
1000VA: CEE 22 recessed plug
AC Output Distribution: 400VA: two Australian 10 ampere receptacles
750VA: four Australian 10 ampere receptacles
1000VA: four Australian 10 ampere receptacles