Setting Reference
42
© Copyright 2018 Softing IT Networks
Setting Reference
It is necessary to perform a set reference measurement if the LOCAL and REMOTE units are being paired
for the first time. If there is a mismatch in firmware versions or a set reference has not been performed,
AUTOTEST will be denied, until these conditions are corrected. Please also verify before testing that
calibrations are not expired.
Note
Diagrams and images used are for illustration purposes only and do not represent
suggested test values. Reference and test values vary to usage and condition.
To set reference,
1.
Connect a Permanent Link adapter to the LOCAL unit.
2.
Connect a Channel adapter to the REMOTE unit.
3.
Connect the 2 units together using the patch cord provided in the kit.
4.
Press the
[TOOLS]
button
Set Reference
5.
Set Reference will fail in the event of-
•
Adapter probe mismatch, i.e., two channel or permanent link adapters
•
Firmware version mismatch between LOCAL and REMOTE units
•
No connection between LOCAL and REMOTE units