Test Procedure
22
© 2019 Softing Singapore Pte Ltd.
The following steps are optional but recommended. If the following steps are not performed, RC and
LC must be used in the tested orientation. Performing steps 10 to 15 will allow both LC and RC to be
used in either orientation.
10.
Interchange the ends of RC.
11.
Press the
[AUTOTEST]
button to perform an AUTOTEST.
12.
Check that the result is less than the acceptable loss limits.
13.
Clean the adaptors and connectors or replace the cords if necessary and repeat the test again.
14.
Interchange the ends of LC.
15.
Repeat steps 1 to 9.
5.1.2
One-cord reference test method
1.
Connect the LC to the LOCAL and REMOTE units.
2.
Press the
[TOOLS]
button
è
Set Reference
and press the
[OK]
button to set reference.
3.
Disconnect LC from the LOCAL unit.
4.
Do not disconnect LC from the REMOTE unit.
5.
Connect one unpinned end of RC to the LOCAL unit and the other end to the pinned end of the
cabling under test.
6.
Connect the disconnected unpinned end of LC to the other pinned end of the cabling under test.
7.
Press the
[AUTOTEST]
button to begin AUTOTEST.