Figure 4: Terminal strip for power supply of the device
1. Connect the cable of a 24 V power supply and the earth conductor (earth terminal) to the terminal
strip on the device. The terminal strip can be plugged and lifted out for installation using a
screwdriver.
2. Connect the cable of the circuit that should be closed by the relay contact to the terminal strip on
the device.
3. Switch on the power supply. The LED RUN is green and the LED ETH flashes red until the device's
boot procedure is completed. Afterwards the LED RUN and BUS light green.
3
Configuring the device in the network
3.1
Configuration requirements
The following ports have to be enabled in the firewall:
Protocol/purpose
Port
HTTP
80 TCP
Firmware update
1100 TCP
TH LINK communication with each other
1123, 1124, 2364 UDP
TH LINK communication with TH SCOPE
via Multicast
via Unicast
2364 UDP
1151, 2365, UDP
3.2
Network presettings
The device is preset to network operation with a DHCP server. No network configuration settings
are required in this operating mode.
In case of manual allocation of IP addresses the device can be reached via the following IP
addresses (Factory setting):
Note
TH LINK can be accessed from office network via IP 169.254.0.1 (default). To access TH LINK
from the automation network, you would choose IP 169.254.0.2 (default).