Implemented protocols in echolink one
Softing Industrial Automation GmbH
31
echolink one2PROFINET V. 1.0
15.1.15
AD 07 00 00 00 00 00 00 01 00 00 00 00 00 00 00
AE 07 00 00 00 00 00 00 03 00 00 00 00 00 00 00
The modification can be seen here:
9.
Byte = Fieldbus Map Adr 6 (Wert = 0x01) => 0x03
A modification of address 7 in the Modbus slave has no consequences to the fieldbus output side
because "No. Of Points = 2" is set in the configuration.
The value stays unchanged on 0x03:
1F 07 00 00 00 00 00 00 03 00 00 00 0
8.8.3.2
Example: Read input status FC2
The following example shows the content of address 10007 ... 10009 is mapped/copied into the
8. fieldbus output byte.
76 09 00 00 00 00 00 00 00 00 01 00 00 00 00