15.1.15
echolink one2PROFINET V. 1.0
24
Softing Industrial Automation GmbH
Implemented protocols in echolink one
Display of the data in the Modbus Master (FC1):
Example: StartAddress 0008, Length 80, FC2 (Read Input Status)
[01] [02] [00] [07] [00] [50] [c9] [f7]
echolink one sends response via RS232/485:
[01] [02] [0a] [02] [03] [04] [05] [06] [07] [08] [00] [00] [00] [8f] [7a]
8.7.1.2
Example: FC3 (Read Holding Register) + FC4 (Read Input Register)
Fieldbus sends to the echolink one
00 30 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 20 20 20...
(The configuration is "Data exchange = On Trigger", with an additonal 1. control byte in the field-
bus data.)
„Fieldbus length byte = active“, in this example 30h (48d), the echolink one copies the following
48 Byte from the fieldbus into the internal storage.
Connected Modbus Master sends request to the RS232/484 side of the echolink one
[01] [03] [00] [00] [00] [14] [45] [c5]
echolink one sends response via RS232/485:
[01] [03] [28] [02] [03] [04] [05] [06] [07] [08] [09] [0a] [0b] [0c] [0d] [0e] [0f] [10] [11] [12] [13] [14]...
... [15] [16] [17] [18] [19] [1a]
Display of the process data in the Modbus Master:
8.7.1.3
Example: Write Single Coil FC5
The Fieldbus Master sent the following data to the echolink one once:
07 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 20 20 20...
1.
Byte = Fieldbus length byte
Содержание echolink one2PROFINET
Страница 41: ...Implemented protocols in echolink one Softing Industrial Automation GmbH 41 echolink one2PROFINET V 1 0 15 1 15...
Страница 57: ...Appendix Softing Industrial Automation GmbH 57 echolink one2PROFINET V 1 0 15 1 15...
Страница 58: ...15 1 15 echolink one2PROFINET V 1 0 58 Softing Industrial Automation GmbH Appendix...
Страница 59: ...Appendix Softing Industrial Automation GmbH 59 echolink one2PROFINET V 1 0 15 1 15...