Sofraser MIVI 9610 Скачать руководство пользователя страница 10

 

Manuel Technique MIVI 9612

 

 

Réf. 254-30/0 

 

10  

2.2.1. Elbow mounting 

 

The flange is welded on a right angle tee as indicated in 

pic.1.  

 

The minimal pipe diameter is of 32 mm. 

 

The flange and the pipe axes have to be the same. 

 

The  flow  direction  is  as  indicated  on  fig.1  (unless  for 

fibrous  fluids  where  the  flow  is  inverted  and  the  rod 
protector removed. (See §2.2.5). 

 

A free area of at least 150 mm length is necessary.  

Advice :  choose  a  sensor  position  in  order  to  assure  a 
permanent  fluid  renewal  and  to  avoid  the  existence  of 
“dead zone”. 

2.2.2. Plane side mounting 

 

The  flange  is  welded  on  a  metal  plate  as  indicated  on 

pic.2.  

 

The free area around the vibrating rod has to be at least 

 40, 150 mm length. 

 

In order to avoid parasitic vibrations, the plate where the 

flange is welded must be thicker than 5 mm. 

Advice : preferably choose a sensor position with the rod 
to  the  top  in  order  to  have  a  total  immersion  of  the 
vibrating rod and to avoid the formation of “dead zone“. 

2.2.3.  Pot mounting, for small flow rates, or pilot plant 

See picture 3. 

2.2.4. Special mountings 

The small sensor size allows numerous personalization 

of  its  fitting  according  to  the  user's  requirements.  Consult 
your distributor. 

2.2.5. Replacement cap 

Each mounting flange is provided with an obturation kit : 

-

 

Cap and O-ring 

-

 

4 fixing screws CHC M6 (or 8 fixing screws M8 for high 

pressure sensor) 

It allows the installation working when the sensor has to be 
removed. 

 

Mounting flange, 

welded

 

15

m

m

 m

in

m

m

 m

ax

int. 

 32 mm mini 

Pic. 1 

¼ 

gas

 

Pic.3

 

On circulation pot 

Earth terminal

 

Pic. 2

 

 

40 mm  mini 

15

m

m

 m

in

17

 

Mounting flange 

welded 

Содержание MIVI 9610

Страница 1: ...Quality System certified instruments 9612 Version Technical Manual MIVI 9610 R f 254 31 0...

Страница 2: ...THE ROD MUST VIBRATE IN AIR 3 INSTALL THE SENSOR ON THE PROCESS AND FIX IT WITH ITS 4 SCREWS 4 REACH THE OFFSET ADJUSTMENT FUNCTION STARTING FROM THE BLOCK SETTINGS AND WITH THE SECURITY CODE 2 5 FOL...

Страница 3: ...2 2 Plane side mounting 10 2 2 3 Pot mounting for small flow rates or pilot plant 10 2 2 4 Special mountings 10 2 2 5 Replacement cap 10 2 3 PRACTICAL ADVICES 11 2 4 CHECKING 11 2 5 SENSOR WIRING 11 2...

Страница 4: ...E 23 6 2 RS485 INTERFACE 23 7 POWER SUPPLY 25 7 1 CHARACTERISTICS 25 7 2 SAFETY CONSIDERATIONS 25 7 3 POWER SUPPLY WIRING 26 8 GENERAL CABLING SCHEMATICS 27 9 SPECIFIC NOTES AND MANUFACTURING PARAMETE...

Страница 5: ...es UTILISATION Mode The UTILISATION Mode makes it possible to visualize in different forms viscosity and temperature values Visualization with bargraphs acquisition graph Access to the sensor identifi...

Страница 6: ...re The rod is vibrating in air When possible note the viscosity information when a cleaning or rinsing solution is flowing If the original calibration is convenient one of the 2 above mentioned values...

Страница 7: ...gas or II 2D dust Ex d IIC T1 to T6 gas Ex tD A21 IP67 T75 C T90 C T125 C T190 C T290 C T300 C dust Be sure the sensor s certification is in accordance with the security level required on your proces...

Страница 8: ...lded on the process line It means it can not be individually certified but with the whole process line 1 6 4 EMC and low voltage directive The processor 9601 is in agreement with EMC specifications de...

Страница 9: ...of the network or reactor If the fluid temperature varies widely and fast choose the upside down or horizontal position in order to allow a convenient air convection among the sensor body It is screw...

Страница 10: ...order to avoid parasitic vibrations the plate where the flange is welded must be thicker than 5 mm Advice preferably choose a sensor position with the rod to the top in order to have a total immersio...

Страница 11: ...to bend the vibrating rod A ring with the same dimensions of the protector s base must be placed on the head of the sensor in order to maintain the O ring IMPORTANT As soon as the sensor is removed s...

Страница 12: ...2 Standard and explosion proof models are both equipped with cable glands Those ones can match the ATEX norm depending on the MIVI version Earth terminal Pic 4 Shielding Cable Receiving coil Driving c...

Страница 13: ...NERAL PURPOSE Ex proof 200 C Std 200 C 135 mm 120 mm 100 mm 17 mm 30 mm Guard tube short slits Pot gas 156 mm 156 mm HIGH PRESSURE HP 200 C HP ex proof 200 C Pot gas Guard tube long slits Low pressure...

Страница 14: ...Technical Manual MIVI 9612 R f 254 30 0 14 2 7 Tightness O ring 29 82 x 2 62 76 or 79 70 or 99 O ring 21 95 x 1 78 O ring 30 00 x 2 00 O ring 30 00 x 2 50 Pic 6...

Страница 15: ...l dimensions Height 80mm Width 100mm Length 160mm Tightness IP66 Material Aluminium Temperature from 0 C to 45 C 3 2 Transducer s electronic board wiring The transducer s board is wired through the co...

Страница 16: ...26 mm Thickness 5mm Weight about 515 g Tightness IP 65 with panel mounting and IP20 on rear panel Operational temperature 0 C to 45 C 4 2 Display Display type STN LCD Illumination backlight LED yellow...

Страница 17: ...ply wiring 4 7 Connection blocks On the processor back module various categories are identified example Digital Inputs Analog Outputs We will call these categories connection blocks The diagram below...

Страница 18: ...oltage 0 10 V current 0 20 mA or 4 20 mA These inputs can be used with thermocouple or Pt100 On 9612 electronics these inputs are connected as 4 20mA and are specific to the plug of a densimeter Four...

Страница 19: ...om 02 to 07 and from 08 to 013 3 A max 250VAC or 30VDC Common 8 A max common plug not written see the connecting plan Minimum load 1mA 5VDC Lifespan 100 000 operations with a maximum load Response tim...

Страница 20: ...in If the user does not have the means to take in charge the wastes of our electronic equipments he should returned these equipments to our factory with a signed letter confirming that it is an equipm...

Страница 21: ...hole for the provided NC6 32 screw Scrape the panel s paint away to ensure the conductive connection Drive the screw into the hole and place the following items first washer ring cable shoe second was...

Страница 22: ...254 30 0 22 Step 4 Push the 4 mounting brackets into their slots on the processor sides shown as follow Step 5 Tighten the bracket screws on the panel Firmly hold the mounting brackets on the process...

Страница 23: ...on 4 RxD signal reception 5 0V reference 6 DSR signal 6 2 RS485 interface RS485 port is used to make the connection between the transmitter and the device Used COM port COM 3 Serial port type RJ 11 Ca...

Страница 24: ...munication capacity up to 32 devices Voltage limits from 7 V to 12 V as max differential Pin number Function 1 A signal red terminal 2 3 4 5 6 B signal white terminal Pins from 2 to 5 are not used for...

Страница 25: ...upply can be used provided that a 0V signal is connected to the frame If the device is mounted on a metal panel standard safety considerations require that the power supply must be earthed to avoid el...

Страница 26: ...the wire do not exceed a maximum torque of 0 5 N m We recommend that you use crimp terminals for wiring Use 26 14 AWG wire for all wiring purposes To maximize the system s performance electromagnetic...

Страница 27: ...cted to the 9612 device Pieces of advice The transducers must all have the same power supply Put a 120 resistance at the end of the line 1 4 W power is enough The RS485 shielding has to be connected t...

Страница 28: ...Technical Manual MIVI 9612 R f 254 30 0 28...

Страница 29: ...erature LOW 0 0 HIGH 999 9 HYST 0 0 HYST 0 0 Alarms attribution CURRENT OUTPUTS Physical value Current output value Viscosity LOW 0 0 4 HIGH 999999 9 20 BURN 4 Temperature LOW 0 0 4 HIGH 999 9 20 BURN...

Страница 30: ...999999 9 999999 9 Line 7 999999 9 999999 9 Line 8 999999 9 999999 9 Line 9 999999 9 999999 9 COMPENSATION TABLE X Y Line 0 0 0 0 0 Line 1 999 9 0 0 Line 2 999 9 0 0 Line 3 999 9 0 0 Line 4 999 9 0 0 L...

Страница 31: ...1 999 0 Line 2 999 0 Line 3 999 0 Line 4 999 0 Line 5 999 0 Line 6 999 0 Line 7 999 0 Line 8 999 0 Line 9 999 0 VISCOSITY ADJUSTMENT A 1 000 B 0 000 CALIBRATION DATA SERIAL N Y0 0 0000 a 1 0000 b 1 00...

Отзывы: