4.3. PV Connection
Procedure
:
Step 1
Select the appropriate cable type and specifications according to the
table4-3.Remove cable glands from the positive and negative connectors.( It is
recommended that the positive and negative be distinguished by different colors).
Step 2
Remove the insulation layer with an appropriate length from the
positive and negative power cables by using a wire stripper as show in Fig.
①
.
Step 3
Insert the stripped positive and negative power cables into the positive
and negative metal terminals respectively and crimp them using a clamping tool.
Ensure that the cables are crimped until they cannot be pulled out by force less than
400 N, as shown in Fig.
②③
.
Step 4
Insert crimped power cables into corresponding housings until you
hear a "click" sound. The power cables snap into place.
Step 5
Reinstall cable glands on positive and negative connectors and rotate
them against the insulation covers.
Step 6
Insert the positive and negative connectors into corresponding PV
terminals of the inverter until you hear a "click" sound, as shown in Fig.
⑥
.
To remove the positive and negative connectors from the inverter, insert a
removal wrench into the bayonet and press the wrench with an appropriate strength,
as shown in Fig.
⑦
.
Before removing the positive and negative connectors, ensure that
the DC SWITCH is OFF.
Fig.4-2 Connect PV
1: Positive metal contact
2: Negative metal contact
①
②
3: Positive connector
4: Negative connector
③
Содержание HYD 3K-6K-EP
Страница 1: ...Shenzhen SOFARSOLAR Co Ltd Energy storage integrated inverter Product Model HYD 3K 6K EP User manual ...
Страница 13: ...HYD 3K 6K EP User manual Copyright Shenzhen SOFARSOLAR Co Ltd 8 ...
Страница 21: ...HYD 3K 6K EP User manual Copyright Shenzhen SOFARSOLAR Co Ltd 16 ...
Страница 36: ...HYD 3K 6K EP User manual Copyright Shenzhen SOFARSOLAR Co Ltd 31 Fig 4 15 Electrical connections Plan A CT ...