SOFAR 3.3~12KTLX-G3
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 55 -
ID166 LogicInterfa
ceDerating Logical interface derating
ID167 AlarmAntiR
efluxing
Anti Refluxing derating
ID169 FanFault1 Fan 1 Alarm
Check whether the inverter has dust and dust,
whether there are foreign matters blocking the fan
at the air inlet. If so, please improve the ventilation
and heat dissipation of the environment. It is
recommended that the inverter should be cleaned
once every half a year.
ID170 FanFault2 Fan 2 Alarm
ID171 FanFault3 Fan 3 Alarm
ID172 FanFault4 Fan 4 Alarm
ID173 FanFault5 Fan 5 Alarm
ID174 FanFault6 Fan 6 Alarm
ID177 Reserved
Reserved
ID178 Reserved
Reserved
ID179 Reserved
Reserved
ID180 Reserved
Reserved
ID181 Reserved
Reserved
ID182 Reserved
Reserved
ID193-
ID224
StringFuse_
Fault0-31
String fuse open circuit
alarm
There are internal faults of inverter, turn OFF the
“DC switch”, wait for 5 minutes, then turn ON the
“DC switch”. Check whether the fault is rectified. If
no, please contact technical support.
ID225-
ID240 Reserved
Reserved
/
Note: the above table is our general fault ID list, all fault IDs of this inverter can
be found in the above table.
7.2. Maintenance
Inverters generally do not need any daily or routine maintenance. But ensure
heat sink should not be blocked by dust, dirt or any other items. Before the
cleaning, make sure that the DC SWITCH is turned OFF and the circuit breaker
between inverter and electrical grid is turned OFF. Wait at least for 5 minutes
before the Cleaning.