SOFAR 3.3~12KTLX-G3
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 50 -
ID49 Reserved
Reserved
Ensure the installation position and installation
method
meet the requirements of this user manual. Check
whether the ambient temperature of the
installation position exceeds the upper limit. If yes,
improve ventilation to decrease the temperature.
Check whether the inverter has dust and dust,
whether there are foreign matters blocking the fan
at the air inlet. If so, please improve the ventilation
and heat dissipation of the environment. It is
recommended that the inverter should be cleaned
once every half a year.
ID50 TempFault_
HeatSink1
Heat sink1
over-temperature
protection
ID51 Reserved
Reserved
ID52 Reserved
Reserved
ID53 Reserved
Reserved
ID54 Reserved
Reserved
ID55 Reserved
Reserved
ID57 TempFault_
Env1
environment
temperature1 protection
ID58 Reserved
Reserved
ID59 TempFault_
Inv1
Model 1
over-temperature
protection
ID60 Reserved
Reserved
ID61 Reserved
Reserved
ID65 VbusRmsUn
balance
Unbalanced RMS value of
bus voltage
There are internal faults of inverter, turn OFF the
“DC switch”, wait for 5 minutes, then turn ON the
“DC switch”. Check whether the fault is rectified. If
no, please contact technical support.
ID66 VbusInstant
Unbalance
Unbalanced
instantaneous value of
bus voltage
ID67 BusUVP
Bus undervoltage during
grid connection
If the configuration of the PV array is correct, could
be the sun irradiation is too low. Once sun
irradiation back to normal, inverter will work back
normal
ID68 BusZVP
Bus voltage is low
There are internal faults of inverter, turn OFF the
“DC switch”, wait for 5 minutes, then turn ON the
“DC switch”. Check whether the fault is rectified. If
no, please contact technical support.
ID69 PVOVP
PV overvoltage
ID70 Reserved
Reserved
ID71 LLCBusOVP LLCBUS overvoltage