Force the battery to charge at a certain time to ensure that the battery is fully charged.
Save
Save the Settings after the Settings are complete
2. Battery Active
Battery Active
1.Auto Active Control
2.Force Active
Use this function to forcibly activate the battery when the battery is low
。
3. Feed-in limitation
Users can limit the maximum power sent from the system to the grid by enabling Anti
Reflux control. Counter current power is the maximum power expected to be sent to
the grid (e.g., 0KW means no energy is fed into the grid).
Feed-in Limitation
1.Feed-in Limitation
Enable/Disable
2.Hard Limit Control
Enable/Disable
3.Feed-in Power
**.*KW
Feed-in Limitation
Determine whether to enable the function
Hard Limit Control
After enabling this function, if the power input to the grid is greater than the power set
for Feed-in limitation power, the machine will enter a recoverable fault state.
Feed-in Power