4.4. External Electrical Connection
4.4.1.
External ground Connection of the PGND cable
Procedure 1 Crimp OT terminals
Precautions
:
When stripping the cable, do not scratch the core of the cable.
The conductor crimping plate of an OT terminal is pressed to form a cavity that
completely covers the conductor core and tightly binds the OT terminal.
The crimping line can be covered with heat shrink tubing or insulation tape.
Figure 4.4.1-1 Diagram of
Crimping OT terminals
Procedure 2
The OT terminal is crimped properly, and the ground cable is connected
to the position shown in the following figure.