75-136KTL
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 34 -
C
RS485
Modbus/DRMs
RS485/DRMs
RS485 Communication
port/DRMs port
D
AC output
terminals
AC output terminal
E
Grounding
Connecting terminal of the
ground, choose at least one for
grounding connection
5.3. Grounding Connection (PE)
Connect the inverter to the grounding electrode using ground cable.
SOFAR 75-136kW is a transformerless inverter which requires the
positive pole and negative pole of the PV array are NOT grounded.
Otherwise, it will cause inverter failure. In the PV system, all
non-current-carrying metal parts (such as mounting frame, combiner
box enclosure, etc.) should be connected to earthed.
Note
Preparation: prepare the grounding cable (recommend 16mm² yellow-green
outdoor cable and M8 OT Terminal)
Procedure:
Step 1
: Remove the insulation layer with an appropriate length using a wire stripper
shown as figure 5-2.
Figure 5-2 Grounding connection instruction
(
1
)
Note
:
the length of L2 should 2~3mm higher than L1.
Step 2
: Insert the exposed core wires into the OT terminal and crimp them by using
a crimping tool, as shown as figure 5.3. Recommend using OT terminal: OT M6,
Cable: ≥6mm
2
.