4. ELECTRICAL REQUIREMENTS
4.6. REFERENCES OF SPARE FUSES
Minimum quantity to order: 10 pieces
Fuse rating
Reference
2A
60DC0002
4 A
60DC0004
6 A
60DC0006
8 A
60DC0008
10 A
60DC0010
12 A
60DC0012
16 A
60DC0016
4.7. SURGYS - SURGE PROTECTION DEVICE (SPD)
Installation
Cable cross-section: 6 mm² to 25 mm².
Maximum cable length: 0.5 m
Respect the rules of the class 2: the ground connecting cable
of the SPD device must not be yellow/green coloured.
PE cable tightening torque: 2.2 Nm
Maintenance
• Check the end of service life indicator of the Surgys.
• Reference of Surgys m-G51-1000PV with remote signal, 2
poles: 49822521
• Reference of spare plug-in module m-G51-1000PV:
49822529
4.8. PERIODIC MAINTENANCE CHECKS
Checklist
• Cable status.
• Box status.
• Connections status.
• Check tightening torques.
• Fuses status.
• DC switch-disconnector status.
• DC switch-disconnector remote trip operation.
• Surgys surge protection device Status (end of life indicators).
Periodicity: once a year minimum.
4.9. STORAGE
The Field Junction Box must be stored appropriately.
• During storage the Field Junction Box must remain in its original packaging.
• The Field Junction Box must be stored in environments free from damp, protected against dust and condensation and exposed
to small variations in temperature.
• Observe the climate conditions in conformity with standard EN 50178.
• Ambient temperature for transport and storage: from -25 °C to +60 °C