MASTERYS BC
from 15 to 20 kVA
14
IT
ALIANOENGLISH
3.5-2
Open the terminal boards protection panel at the back of the UPS by removing the four fastening screws
A
.
The terminal board shown is the most complete version including all options. In the basic mod-
els or in the versions with internal batteries the terminal board has fewer terminals. Refer to
the names of each terminal to identify it during connection. After connection secure the cables
with bands
C
(figure 3.5-3) to couplings
B
as shown in the figure 3.5-5.
3.5-3
Connect the ground lead to the terminal with the corresponding symbol. Connect the input cables to
the terminals labelled “MAINS SUPPLY”
L1
,
L2
,
L3
,
N
(observing the phase cycle direction).
3.5-4
Connect the cables of the separate auxiliary power supply (if present) to the terminals labelled “AUX
MAINS SUPPLY”
L11
,
L21
,
L31
,
N1
(observing the phase cycle direction).
In the event of a UPS with 15-20 kVA single-phase output, it is
essential to connect the auxiliary mains to the relative dedicat-
ed terminal board. If there is no separate mains for the bypass, it
is advisable to obtain one from the primary mains in one of the
two ways set out below:
• with distribution external to the UPS (figure .5-6).
• with a bridge connection (figure .5-7).
3.5-8
Connect the output cables to the terminals labelled “OUTPUT”
L12
,
L22
,
L32
,
N2
.
3
UNPACKING AND INSTALLATION
OF THE UNIT
L1
5
L2
5
L3
5
N5
POWER SHARE
OUTPUT
L1
2
L2
2
L3
2
N2
EXTERNAL BATTERY
+B2
–B2
–B1
+B1
AUX MAINS SUPPLY
L1
1
L2
1
L3
1
N1
MAINS SUPPLY
L1
L2
L3
N
8 cm ma
x
3.5-8
L1
5
L2
5
L3
5
N5
POWER SHARE
OUTPUT
L1
2
L2
2
L3
2
N2
EXTERNAL BATTERY
+B2
–B2
–B1
+B1
AUX MAINS SUPPLY
L1
1
L2
1
L3
1
N1
MAINS SUPPLY
L1
L2
L3
N
3.5-4
L1
5
L2
5
L3
5
N5
POWER SHARE
OUTPUT
L1
2
L2
2
L3
2
N2
EXTERNAL BATTERY
+B2
–B2
–B1
+B1
AUX MAINS SUPPLY
L1
1
L2
1
L3
1
N1
MAINS SUPPLY
L1
L2
L3
N
3.5-7
OUTPUT
L1
2
N2
EXTERNAL BATTERY
+B2
–B2
–B1
+B1
L11A = L11
N1A = N1
AUX MAINS
SUPPLY
L11A
N1A
L1
1
N1
MAINS SUPPLY
L1
L2
L3
N
L1
5
L2
5
L3
5
N5
POWER SHARE
L2 L3
L1 N
3.5-6
Mains
AUX Mains
Mains
3.5-2
A
C
3.5-5
B
3.5-3