5
EN
DIRIS DIGIWARE - 546420C - SOCOMEC
2. HazarDs anD warnings
The term "device" used in the following paragraphs encompasses DIRIS Digiware.
The assembly, use, servicing and maintenance of this equipment must only be carried out by trained, qualified
professionals.
socomec shall not be held responsible for failure to comply with the instructions in this manual.
2.1. risk of electrocution, burns or explosion
Caution: risk of electric shock, burns or explosion. Do not use
DIRIS Digiware S for voltage testing purposes. A voltage tester
must be used instead. Failure to follow these instructions will result
in death or serious injury.
Ref. ISO 7000-0434B (2004-01)
Caution: refer to the accompanying documentation each time this
symbol is shown
Ref. ISO 7000-0434B (2004-01)
• Only duly authorised and qualified personnel may work or install/uninstall the device.
• The instructions are valid together with the specific instructions for the device.
• The device is designed only for its intended purpose as set out in the instructions.
• Only accessories authorised or recommended by SOCOMEC may be used in association with the device.
• Before proceeding with installation, maintenance, cleaning, disassembly, connection, or maintenance work, the
device and system must be cut off from the mains to avoid electrocution and damaging the system and device.
• This device is not designed to be repaired by the user.
• For any questions related to the disposal of the device, please contact SOCOMEC.
Failure to comply with the instructions of the device and this safety information can cause bodily injury,
electric shock, burns, death or damage to property.
2.2. risk of damaging the device
Caution: risk of electric shock
Ref. ISO 7000-0434B (2004-01)
Caution: refer to the accompanying documentation each time this
symbol is shown
Ref. ISO 7010-W001 (2011-05)
To ensure that the device operates correctly, make sure that:
• The device is correctly installed.
• The auxiliary power supply voltage indicated on the device is observed: 24 VDC ± 15%.
• The use of a SOCOMEC 230 VAC / 24 VDC power unit or a 24 VDC max 20 W class 2 power unit / SELV. The
device must be protected with a 1A 24 VDC fuse.
• The network frequency indicated on the device is observed: 50 or 60 Hz.
• A maximum voltage at the voltage input terminals of 520 VAC phase/phase or 300 VAC phase/neutral is
observed.
• Always connect the DIRIS Digiware S device observing the maximum prescribed currents (63A).
• Only use RJ45 SOCOMEC cables to interconnect the modules via the Digiware bus. When the ambient
temperature e50°C, the minimum temperature rating of the copper cable to be connected to terminal
must be +85°C.
• The device must not be cleaned.
• The device must not be installed outdoor.
Failure to respect these precautions could cause damage to the device.