13.3. system alarms
If an installation error is detected during setup, a system alarm is automatically generated.
13 .3 .1 . Voltage/current association
• Alarm upon connection error: wrong association between the current inputs of the DIRIS Digiware S module and
the voltage inputs on the DIRIS Digiware U module
13 .3 .2 . Incorrect direction of rotation (three-phase network)
• Alarm upon identification of the incorrect direction of phase rotation (for example 3-2-1 instead of 1-2-3)
13.4. Protection alarms
DIRIS Digiware S modules have 6 protection alarms alerting the user of an event on a protective device.
Make sure you have configured the protective device type used in the “Loads” configuration menu in order to use
the Protection alarms.
The protection alarms can be based on the opening of the protective device, the Tripping of the circuit breaker, or
the defect of the protective device.
Example of configuring a protection alarm via Easy Config
13.5. setting up alarms
Alarms can be activated or deactivated from the Easy Config configuration software.
There are several ways of identifying the presence of an alarm:
13 .5 .1 . LED on front of module
• Blinking: System alarm
• Fixed: Alarm upon event (has priority over system alarms when both alarms are on-going at the same time)