SOCOMEC - Ref. : 875 092A
29
ENGL
ISH
COMMUNICATION (continued)
Reset to zero
274
112
1
Meter index
1 to 7: totalizer meter
from 1 to 7
8 to 11: value between two
signals for input
1 to 4
12 to 18: meters history file
19: all values
(1 to 18)
275
113
1
Reset validation
0 = no / 1 = yes
Zone size (1): 20 words in decimal or 14 in hexadecimal
Automatic synchronisation and save
Address
SETTING OR DISPLAY OF INPUTS CONFIGURATION
Decimal
Hexadecimal
N° of words (1)
Description
Unity
256
100
1
Input 1 allocation
0=Pulse / 1=Energy
257
101
1
Input 2 allocation
0=Pulse / 1=Energy
258
102
1
Input 3 allocation
0=Pulse / 1=Energy
259
103
1
Input 4 allocation
0=Pulse / 1=Energy
260
104
1
Input 5 allocation
0=Pulse / 1=Energy
261
105
1
Input 6 allocation
0=Pulse / 1=Energy
262
106
1
Input 7 allocation
0=Pulse / 1=Energy
263
107
1
Input 1 scale (if energy)
264
108
1
Input 2 scale (if energy)
265
109
1
Input 3 scale (if energy)
0=0,01 kWh / 1=0,1 kWh
266
10A
1
Input 4 scale (if energy)
267
10B
1
Input 5 scale (if energy)
4=100 kWh / 5=1000 kWh
268
10C
1
Input 6 scale (if energy)
269
10D
1
Input 7 scale (if energy)
270
10E
1
Synchronisation of average values
0=8 min/1=10 min/
if input 1 to 4 in energy)
2=15 min/3=20 min/4=30 min
271
10F
1
Storage day
from 1 to 28
272
110
1
Hour
from 0 to 23
273
111
1
Minute
from 0 to 59
2=1 kWh / 3=10 kWh
Example: configuration of input n° 1 / Countis Ci n° 5.
Response: identical to the question
Slave
Function
Address
Number of words
CRC16
05
06
01
00
00
01
4CCA
High value
Low value
High value
Low value
CONFIGURATIONS SETTING OR DISPLAY
INPUTS, AUTOMATIC READING AND RESET (FUNCTIONS 3, 6 OR 16)