13.9.
Communication (optional 9383 xxxx units only)
13.9.1. COMM Menu
1
2
Variable
Definition
Adjustment range
Default value
1
2
Address
Address of the device
1 to 255
5
1
2
Speed
Communication speed
2400, 4800
9600, 19200
38400
9600
1
2
Stop bit
1, 2
1
1
2
Parity
NO, ODD, EVE
NO
Only available on ATyS p M version with Comm.
RS485
2 or 3 wire half-duplex
Protocol
MODBUS® protocol in RTU Mode
Speed
2400, 4800, 9600, 19,200, 38,400 Bauds
Galvanic insulation
2.5 kV (1 min 50 Hz)
13.9.2.
General Information
Communication via an RS485 connection (Modbus
®
protocol) enables you to connect up to 31 ATyS to a PC or a
programmable logic controller over a distance of 1200 metres.
• Recommendations
You should use a shielded twisted pair (LIYCY type).
If the distance of 1200 m and / or the number of 31 ATyS is exceeded, it is necessary to connect a repeater to enable
an additional connection of ATyS over more than 1200 m. For further information on the connection methodology,
please consult us.
N 1
N 2
N n
R = 120 Ω
1200 M or 32 UL
R = 120 Ω
PLC
Other systems
N 1
R = 120 Ω
repeater
RS485
+ - - +
N n
R = 120 Ω
max 1200 M or 32 UL
max 1200 M or 32 UL
PLC
Other systems
R = 120 Ω
R = 120 Ω
It is essential to have a 120 ohm termination at both ends of the bus. This termination is selectable on
the ATyS p M close to the RS485 connection terminal.