INSTALLATION OF OPTIONAL ACCESSORIES
9.1. Auxilliary contacts
Ref. 1309 1001 or ref. 1309 1011.
To fit an AC, the switch must first be put in the 0 position. An auxiliary contact module comprises: one NO/NC
changeover contact for each position (I-0-II). To install use the screws supplied with the module.
Pozidriv PZ2 - 1 Nm
Use 20mm
screws for 1
module
Use 35mm
screws for 2
modules
0,5 to 2,5 mm²
solid
stranded
0,5 to 1,5 mm²
10 mm
PUSH-IN
9.2.
Voltage sensing and power supply tap
Ref. 1399 4006.
This provides 2 connection terminals for conductors with cross-section ≤ 1.5 mm².
The single pole terminals can be fitted in any of the terminal cages without reducing the cage connection capacity.
2 parts/ref. Do not use in case of use of the bridging bar.
Slotted head 3,5 mm
0,45 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
9.3.
Bridging bars 4P
Ratings ≤ 125A: ref. 1309 4006; 160A : ref. 1309 4016
RJ
RS
207208209210
43 44 53 54 63 64 73 74
2
4
6
8
1
3
5
7
2
4
6
8
1
3
5
7
2
4
6
8
1
3
5
7
2
4
6
8
1
3
5
7
/
RJ
RS
207208209210
43 44 53 54 63 64 73 74
/
2
4
6
8
1
3
5
7
2
4
6
8
1
3
5
7
2
4
6
8
1
3
5
7
2
4
6
8
1
3
5
7
LOAD
OK
NOK
LOAD
Source I
Source I
Source II
Source II
Hexagonal Metric
Allen size 4
5,0 Nm
Allen size 4
Hexagonal Metric
44,1 lb-in 5,0 Nm
15 mm / 0,59 "
# 8 to # 00 AWG
10 to 70 mm
2
6 to 70 mm
2
*
# 10 to # 00 AWG
!
X8
Allen size 4
Hexagonal Metric
44,1 lb-in 5,0 Nm
15 mm / 0,59 "
# 8 to # 00 AWG
10 to 70 mm
2
6 to 70 mm
2
*
# 10 to # 00 AWG
!
X8
Load side
bridging bar.
125A: 1309 4006
160A: 1309 4016
10 to
70 mm²
15mm
Make sure that the bridging bar is fitted to the correct set of terminals.
There are two references available: one for ratings up to 125A, and another for 160A rating.
!