EN
ATyS p M - 542935E - SOCOMEC
13.5.10.2. Outputs description
M-G* M-M*
Source available
•
•
S1A /S2A
Source
I
/ Source
II
available. Output activated (closed) if source
I
/ source
II
is within
the defined setting ranges (same function as LED on front panel).
At least one source available
•
•
SCA
Source
I
or
II
available. Output activated (closed) if at least one of the 2 sources is within the
defined settings ranges.
Position auxiliary contact
•
•
AC1/AC2/
AC0
Outputs activated respectively when product is in position I / position II / position 0.
Load supplied by source
I
/ by source
II
•
•
LO1 / LO2
Indicates which source is supplying the load. Output LO1 / LO2 activated if the 2 following
conditions are simultaneously validated: position I / position II is closed and source
I
/ source
II
is available (LO1 = AC1 et S1A / LO2 = AC2 et S2A). position I / position II is closed and
source / source is available (LO1 = AC1 and S1A / LO2 = AC2 and S2A).
Load shedding command
•
•
LSC
Load shedding relay. Initiates a load shedding action before transfer to back-up source, and
then reloading after restoration. Operations see following pages.
Fault summary
•
•
FLT
Output activated (closed) if at least one fault (internal or transferred external) is activated.
Product operational (no fault + product in Auto mode)
•
•
POP
Output activated (closed) if the product is deemed "operational" i.e. it is in AUT mode, the
supply is present and no fault is detected.
Input copy
•
•
CP1/CP2/
CP3
The output adopts the same status as input 1 / input 2 / input 3. Same function as relaying.
Synthesis TON
•
TOS
Output is activated in case of test on load.
Synthesis EON
•
EOS
Output is activated in case of external on load.
Synthesis TON and EON
•
ROS
Output is activated in case of test on load or external on load.
Output parameter for programmed start of the genset (Linked to EET time delay)
•
EES
This parameter activates an output that can be linked to the inputs EON or EOF in order to test the
genset during a time defined respectively by (E1T, E2T, E3T) and (E5T, E6T, E7T).)
Product in Manual Mode
•
•
MAN
This Output is activated when the product is in Manual Mode (Cover open).
Fail start output
•
FST
Output is activated in case of generator fail start.
* M-G : network - genset application - M-M: network - network application