©2009 NETCONS, s.r.o.
Page 15 of 27
INF, to send
STATUS
message by SMS to number preconfigured by the
ALARMNUMBER
command (e.g.
ALAR421903123456
, see
chapter Alarms)
Example of SCHEDULER? command output (four actions were recorded):
o
11:00,*,ON Turn on Main switched output every day at 11:00
o
14:30,*,OFF Turn off Main switched output every day at 14:30
o
01:30,1,RES Restart Main switched output every Monday at 01:30
o
19:00,5,INF Send Status SMS every Friday at 19:00
3.9
Counters
Six independent counters increments their status upon change on IQSD-GSM
inputs and outputs.
SMS Command
Description
SMS Response
Type
COUNTER1?
Get status of Counter1, increments
on change of Digital Input1
COUNTER1=0
Ctrl
COUNTER2?
Get status of Counter2, increments
on change of Digital Input2
COUNTER2=0
Ctrl
COUNTER3?
Get status of Counter3, increments
on change of Main switched output
COUNTER3=0
Ctrl
COUNTER4?
Get status of Counter4, increments
on change of Aux switched output
COUNTER4=0
Ctrl
COUNTER5?
Get status of Counter5, increments
on pressing of Push Button
COUNTER5=0
Ctrl
COUNTER6?
Get status of Counter6, increments
on loosing registration into GSM
network
COUNTER6=0
Ctrl
COUNTERX?
Get status of all counters
COUNTER=0,0,0,0,0,0
Ctrl
CLEARCOUNTER1
Clear status of counter 1 (2-6)
CLEARCOUNTER1- OK
Ctrl
CLEARCOUNTERALL Clear status of all counters
CLEARCOUNTERALL- OK
Ctrl
Counter1 is incremented by 1 after commands
RESTART
,
TURNOFF
,
TURNON
Highest possible status of a counter is 65535.
3.10
Alarms
IQSD-GSM supports three independent alarms.
Alarm invoked by change on inputs, having highest priority
AC mains power failure alarm
Backup battery remaining charge alarm, having lowest priority