7
SS004V2
Condition
Number
Wiring
Conditions
Supply Terminal
LED
Buzzer
N
E
L
Socket Wiring
1
Correct
N
E
L
Continuous
2
L-E reverse
N
L
E
Warble
3
L-N-E
miswire
E
L
N
Warble
4
L-N reverse
L
E
N
Warble
5
L-N-E
miswire
L
N
E
Warble
6
Faulty N/L-E
miswire
NC
L
N
Warble
7
Faulty N/E
miswire
NC
N
L
Warble
8
Faulty N
NC
E
L
Warble
9
Faulty N/L-E
reverse
NC
L
E
Warble
10
Faulty E/L-N
reverse
L
NC
N
Warble
11
Faulty E
N
NC
L
Warble
12
Faulty E/N
miswire
E
NC
L
Warble
13
Faulty E/L-N
miswire
L
NC
E
Warble
14
Faulty L/N-E
miswire
L
N
NC
Warble
15
Faulty L/E
miswire
N
L
NC
Warble
16
Faulty L/N-E
miswire
E
L
NC
Warble
17
Faulty L/N
miswire
L
E
NC
Warble
18
No mains
NC
NC
NC
None
LED’s will flash to indicate a fault.
NC = No connection