Socket & See PDL 234Plus Скачать руководство пользователя страница 6

6

SS004V2

3.1.4 No Trip Loop Testing

A brief press of the test button will initiate the loop test. Three socket test LED’s
will flash orange to indicate a loop measurement is being taken. The result will
then be displayed on the Fault loop results LED’s . For a guide to results please
see the below table.

FOR GUIDANCE ONLY: Refer to the IET Wiring standards BS 7671

< 1

Less than 1 Ohm: A good result and typical of a correctly wired
TN (PME) system.

< 2

Less than 2 Ohm: A result that would be worth pushing the plug
in and out to see if it is just tarnished socket contacts or
checking where the socket is located. If it is at the furthest point
of the end circuit a higher reading may be expected.

<100

Less than 100 Ohms: Now you must check the wiring system
being used. If it is a TT system (earth rod) then it is a good result
but if it is any other system this should cause concern and urgent
investigation is required.

< 200

Less than 200 Ohms: As above. Assuming it is a TT system most
codes of practice accept a Loop Test value of less than 200
Ohms for an earth rod for a system protected by a 30mA RCD
as being acceptable.

>200

There are very real problems  with this system and urgent further
investigation is requited

Содержание PDL 234Plus

Страница 1: ...Instruction Manual Specification PDL 234Plus Part P Loop Testing Kit SS004V2 Sn...

Страница 2: ...been designed to be used with suitable PPE including insulated gloves if required Caution refer to the instruction manual Construction is double insulated Product should be recycled as electronic was...

Страница 3: ...nderstand LED indication Quick and convenient non trip loop impedance test Mains voltage indication Incoming mains polarity test Socket wiring tester Carrying case included Contains 13A plug to IEC co...

Страница 4: ...ts AC LED INDICATION 207 AMBER 207 253 GREEN 253 RED Fault loop result LED s Table of correct and common socket wiring faults Polarity test indications Socket wiring and Polarity status LED s Mains vo...

Страница 5: ...en DO NOT PROCEED Investigation and remedial action is required before any further tests can be carried out 3 1 2 Incoming Supply Polarity Test With all three LED s illuminated green place your thumb...

Страница 6: ...ug in and out to see if it is just tarnished socket contacts or checking where the socket is located If it is at the furthest point of the end circuit a higher reading may be expected 100 Less than 10...

Страница 7: ...le 7 Faulty N E miswire NC N L Warble 8 Faulty N NC E L Warble 9 Faulty N L E reverse NC L E Warble 10 Faulty E L N reverse L NC N Warble 11 Faulty E N NC L Warble 12 Faulty E N miswire E NC L Warble...

Страница 8: ...rasives or solvents There are no user serviceable parts Contact Socket and See for parts and technical assistance Socket and See Century Road High Carr Business Park Newcastle Staffordshire UK ST5 7UG...

Страница 9: ...uracy to 1 and displayed on 3 LED s 207 VAC LOW 207 253 VAC STANDARD 253 VAC HIGH Loop Test No trip mode 3 wire testing Phase Neutral Earth all connected Test current 15mA at 253V AC Range Accuracy 1...

Страница 10: ...See fused test leads SOC ITLS400 Specification Continued Overvoltage Category CAT III 300 V Over Voltage Protection 440V AC No damage complete recovery Operating Temperature 0 C to 40 C Operating Hum...

Отзывы: