765042231 Rev.001
i7 -1 240
s
(5)
5
high pressure alarm signalling delay (“HP”
code)
-1 = the alarm will not be signalled
Par.
Min.
Max.
Unit
EVX803..02
SBU 15
EVX803..01
SBU 20/40
Digital outputs
u1
0
1
- - - -
0
0
utility managed by the output K4 (16)
0 = door resistances (in this case,
parameter u5 will assume
significance)
1 = condenser fan (in this case, the P5,
F11 and F12 parameters will assume
significance)
u2
0
1
- - - -
0
0
enabling of cabinet light switch-on/off in
manual mode during "stand-by" status (17)
1 = yes
u5 -50.0 99.0 °C/°F
(1)
-7.0
-7.0
cabinet temperature over which the door
resistances are off (4)
u6 1 240 min
1
1
if parameter u11 is set at 1, maximum
duration of needle probe heating; see also
parameter u7
if parameter u11 is set at 2, duration of UV
light switch-on for the sterilisation cycle
u7 -50.0 99.0 °C/°F
(1) -50.0
-50.0
needle probe heating end temperature
(temperature detected by the needle probe);
also see parameter u6
u11
0
2
- - - -
1
1
utility managed by the output K5 (16)
0 = (in this case, the AUXILIARY key and
parameters i0 and u2 will assume
significance)
1 = (in this case, the AUXILIARY key and
parameters u6 and u7 will assume
significance)
2 = (in this case, the AUXILIARY key and
parameter u6 will assume
significance)
Par.
Min.
Max.
Unit
EVX803..02
SBU 15
EVX803..01
SBU 20/40
Serial communication (MODBUS)
LA
1
247
- - - -
(247)
(247)
device address