51
765042231 Rev.001
i0
0
2
- - - -
2
2
effect caused by opening the door, i.e. by
activation of the door micro switch (14)
0 = no
effect
1 = the compressor and the evaporator
fan will be off and the cabinet light
will be on. On expiry of the time
established with parameter i2, the
display will show the flashing “id”
code and the buzzer will be activated
(until the door is closed); also see
parameter F15 (15)
2 = the evaporator fan will be off and the
cabinet light will be on. On expiry of
the time established with parameter
i2, the display will show the flashing
“id” code and the buzzer will be
activated (until the door is closed);
also see parameter F15
i1
0
1
- - - -
1
1
type of door micro switch input contact
0 = normally open (input active with
closed contact)
1 = normally closed (input active with
open contact)
i2 -1 120 min
1
1
door open alarm signalling delay (“id” code);
on expiry of the time established with the
parameter, the compressor will be off
-1 = the alarm will not be signalled
i5
0
1
- - - -
0
1
effect caused by the activation of the high
pressure input
0 = no
effect
1 = the compressor and the evaporator
fan will be off and the condenser fan
will be on. On expiry of the time
established with parameter i7, the
display will show the flashing “HP”
code and the buzzer will be activated
(until the input is deactivated)
i6
0
1
- - - -
(0)
1
type of high pressure input 1
0 = normally open (input active with
closed contact)
1 = normally closed (input active with
open contact)