GT INSTALLATION AND OPERATION INSTRUCTIONS
Page 9
Figure 13 - Wall Penetration Detail
The debris screen provided with the boiler must be
installed in the concentric terminal as shown in Figure
14.
Figure 14 - Debris Screen Installation
VERTICAL DIRECT VENT SYSTEMS
Read the information in the GENERAL VENTING
GUIDELINES section before proceeding.
The GT can be vented vertically directly through the
building’s roof or through a dormant chimney used as
a chase, Figures 15 & 16. All roof penetrations must be
properly fl ashed and sealed.
WARNING: Under no conditions, shall this boiler
vent gases directly into a masonry chimney
nor can an active chimney be used as a chase.
Failure to comply with this warning can result in
excessive levels of carbon monoxide which can
cause severe personal injury or death!
Separate Air Intake and Vent Terminals
The discharge of the vent terminal must point away
from the pitch of the roof. The vent terminal must be a
minimum of
18 in
,
457 mm
, above the air inlet terminal.
The vent terminal must also be
24 in
,
610 mm
, above
any roof surface within a horizontal distance of
10 ft
,
3 m
. The air inlet terminal must always be a minimum
of
12 in
,
305 mm
, plus the snow allowance above
any surface that will support snow, however a snow
allowance of
24 in
,
610 mm
, is highly recommended
Figures 15 & 16.
Consult your weather office for the maximum typical
snowfall for your region. For example, in Boston MA the
maximum typical snowfall is
12 in
,
305 mm
. Therefore
the inlet must be
24 in
,
610 mm
, above any surface that
will support snow. The exhaust must be
42 in
,
1067 mm
,
above this surface.
Figure 15 - Two Pipe Through the Roof
The horizontal centerline distance between the inlet
and exhaust terminals must be a minimum of
4 in
,
102 mm
. If the horizontal distance between the inlet
and exhaust is more than
12 in
,
305 mm
, increase
the ver tical separation by the same amount. For
example, if the horizontal separation is
24 in
,
610 mm
,
a minimum ver tical separationof
30 in
,
762 mm
,
is required,
18 in
,
457 mm
, +
12 in
,
305 mm
, =
30 in
,
762 mm
. If the horizontal distance is greater then
6 ft
,
1.8 m
no additional vertical spacing is required.
The vertical separation is never required to be greater
then
36 in
,
914 mm
.
A dormant chimney can be used as a chase through
which the air intake and vent pipes can be run, Figure
16. The chimney must not be connected to a fi replace,
water heater or any other heating appliance.
Figure 16 - Two Pipe Using Dormant Chimney
Содержание GT-150
Страница 19: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 19 Figure 30 Multiple 4 Wire Zone Valves...
Страница 22: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 22 Figure 33 Boiler Ladder Diagram...
Страница 23: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 23 Figure 34 Boiler Connection Diagram...
Страница 38: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 38 Figure 48 Replacement Parts Exploded View SIOM 36...
Страница 40: ...WESTCAST INC 260 NORTH ELM STREET WESTFIELD MA 01085 TEL 413 562 9631 FAX 413 562 3799...